+ DEHNguard® SE CI with integrated Backup Fuse

Modular surge arrester with integrated backup fuse

For protecting low-voltage consumer's installations against surges. For installation in conformity with the lightning protection zone concept at the boundaries from 0B– 1 and higher.
  • Arrester backup fuse integrated in the protection module
  • For use in case of higher rated voltages
  • Energy coordination with other arresters of the Red/Line product family
  • High discharge capacity
  • High reliability due to "Thermo Dynamic Control" SPD device monitoring
  • Easy replacement of protection modules without tools due to module locking system with module release button

Version

DEHNguard SE CI 440 FM: Modular single-pole surge arrester with integrated backup fuse (floating changeover contact)
DEHNguard SE CI WE 440 FM: Modular single-pole surge arrester with integrated backup fuse particularly for use in wind turbines (floating changeover contact)

Details

The modular surge arrester of the DEHNguard SE CI product family for systems with higher rated voltages of 400 / 690 V is available as type DG SE CI 440 FM and DG SE CI WE 440 FM. Type WE is equipped with a varistor of 750 V rated voltage and therefore is perfectly suited for converter operation with voltage peaks, for example in wind turbines.
With the already integrated arrester backup fuse the user no longer has to care about arrester-specific dimensioning requirements such as backup protection in the event of short-circuit and impulse current carrying capability.
Highest system availability even in case of higher voltages due to the ideal matching of SPD and integrated backup fuse. The integrated backup fuse has been developed especially for this case of application. It is not designed for continuous current but rather for impulse current and short-circuit protection which ensures optimal performance. The fuse only being tripped in case of end of SPD's service life, separate replacement is not necessary.
Due to the "Thermo Dynamic Control“ monitoring device, the surface temperature of the heavy-duty varistor and the intensity of the discharge current are used for evaluation. The operating state of each protective path is shown by means of a mechanical indicator with green and red indicator flags which needs no power to operate. It also indicates the activation of the "Thermo Dynamic-Control“ monitoring device and of the integrated arrester backup fuse.
In addition to this mechanical operating state / fault indication the versions of the DEHNguard SE CI (WE) 440 FM devices feature a three-pole remote signalling terminal. With its floating changeover contact, the remote signal can be used as break or make contact according to the particular circuit concept.
All benefits of the modular design of the DEHNguard family have been integrated into the new DEHNguard SE CI family.
The unique module locking system prevents the protection modules from becoming loose due to vibration during transport or the enormous forces of discharge.
The pluggable protection modules are mechanically coded which is an additional safety feature of these DEHN devices and ensures against installing an incorrect protection module.

Models

DEHNguard SE CI 440 FM

DEHNguard SE CI WE 440 FM

DEHNguard SE CI 440 FM

Basic circuit diagram DG SE CI 440 FMDimension drawing DG SE CI 440 FM

Modular single-pole surge arrester comprising a base part and a plug-in protection module; with integrated backup fuse and remote signalling contact for monitoring unit (floating changeover contact).


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal a.c. voltage (UN)
Max. continuous operating voltage (a.c.) (UC)
Nominal discharge current (8/20 µs) (In)
Voltage protection level (UP)
Response time (tA)
Max. mains-side overcurrent protection
Rated breaking capacity of the internal backup protection
Short-circuit withstand capability (ISCCR)
Temporary overvoltage (TOV) (UT) – Characteristic
Temporary overvoltage (TOV) (UT) – Characteristic
Operating temperature range (TU)
Operating state / fault indication
Number of ports
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Place of installation
Degree of protection
Capacity
Approvals
Type of remote signalling contact
Switching capacity (a.c.)
Switching capacity (d.c.)
Cross-sectional area for remote signalling terminals
Weight
GTIN
PU
Part No.
  • DG SE CI 440 FM
  • 952 920 +
  • type 2 / class II
  • type 2 + type 3
  • 400 V (50 / 60 Hz)
  • 440 V (50 / 60 Hz)
  • 12.5 kA
  • ≤ 2 kV
  • ≤ 25 ns
  • not required
  • 25 kA
  • 25 kArms
  • 580 V / 5 sec. – withstand
  • 765 V / 120 min. – safe failure
  • -40 °C ... +80 °C
  • green / red
  • 1
  • 1.5 mm2 solid / flexible
  • 35 mm2 stranded / 25 mm2 flexible
  • 35 mm DIN rails acc. to EN 60715
  • thermoplastic, red, UL 94 V-0
  • indoor installation
  • IP 20
  • 1.5 module(s), DIN 43880
  • KEMA
  • changeover contact
  • 250 V / 0.5 A
  • 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
  • max. 1.5 mm2 solid / flexible
  • 161 g
  • 4013364322622
  • 1 pc(s)
  • 952 920
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram DG SE CI 440 FM
      open PDF
      Dimension drawing DG SE CI 440 FM
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      Modular and pluggable single-pole surge arrester 
      with integrated backup fuse, width of  1.5 modules
      With remote signalling contact
      Tyep 2 SPD according to EN 61643-11
      Max. continuous operating voltage:	    440 V a.c.
      Voltage protection level:							<= 2 kV
      Nominal discharge current: 					12.5 kA
      No additional backup fuse required in installations up to a  
      max. short-circuit current of 25 kArms
      Energy coordination according to DIN EN 62305-4
      Arrester of the Red/Line series
      Mech. fault indication for the arrester and integrated backup fuse

      delivery and installation.

      Brand: DEHN
      Type: DG SE CI 440 FM
      Part No.: 952 920

      or equivalent.
      Installation Instructions
      Certificates
      71-101107
      CE_DG_SE_CI_440_FM
      CAD-Data for registered Users
      972125.stp
      972125.igs
      972125.jt
      972125.dwg
      952930m_E.dxf

DEHNguard SE CI WE 440 FM

Basic circuit diagram DG SE CI WE 440 FMDimension drawing DG SE CI WE 440 FM

Modular single-pole surge arrester with a rated varistor voltage Umov = 750 V a.c.; comprising a base part and a plug-in protection module; with integrated backup fuse and remote signalling contact for monitoring unit (floating changeover contact).


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal a.c. voltage (UN)
Max. continuous operating voltage (a.c.) (UC)
Rated varistor voltage (a.c.) (Umov)
Nominal discharge current (8/20 µs) (In)
Voltage protection level (UP)
Response time (tA)
Max. mains-side overcurrent protection
Rated breaking capacity of the internal backup protection
Short-circuit withstand capability (ISCCR)
Temporary overvoltage (TOV) (UT) – Characteristic
Temporary overvoltage (TOV) (UT) – Characteristic
Operating temperature range (TU)
Operating state / fault indication
Number of ports
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Place of installation
Degree of protection
Capacity
Approvals
Type of remote signalling contact
Switching capacity (a.c.)
Switching capacity (d.c.)
Cross-sectional area for remote signalling terminals
Weight
GTIN
PU
Part No.
  • DG SE CI WE 440 FM
  • 952 923 +
  • type 2 / class II
  • type 2 + type 3
  • 400 V (50 / 60 Hz)
  • 440 V (50 / 60 Hz)
  • 750 V
  • 12.5 kA
  • ≤ 3 kV
  • ≤ 25 ns
  • not required
  • 25 kA
  • 25 kArms
  • 580 V / 5 sec. – withstand
  • 765 V / 120 min. – withstand
  • -40 °C ... +80 °C
  • green / red
  • 1
  • 1.5 mm2 solid / flexible
  • 35 mm2 stranded / 25 mm2 flexible
  • 35 mm DIN rails acc. to EN 60715
  • thermoplastic, red, UL 94 V-0
  • indoor installation
  • IP 20
  • 1.5 module(s), DIN 43880
  • KEMA
  • changeover contact
  • 250 V / 0.5 A
  • 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
  • max. 1.5 mm2 solid / flexible
  • 167 g
  • 4013364322639
  • 1 pc(s)
  • 952 923
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram DG SE CI WE 440 FM
      open PDF
      Dimension drawing DG SE CI WE 440 FM
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      Modular and pluggable single-pole surge arrester 
      with integrated backup fuse, width of  1.5 modules
      With remote signalling contact
      Tyep 2 SPD according to EN 61643-11
      Max. continuous operating voltage:	    440 V a.c.
      Rated varistor voltage:                             750 V a.c.
      Voltage protection level:							<= 3 kV
      Nominal discharge current: 					12.5 kA
      No additional backup fuse required in installations up to a  
      max. short-circuit current of 25 kArms
      Energy coordination according to DIN EN 62305-4
      Arrester of the Red/Line series
      Mech. fault indication for the arrester and integrated backup fuse

      delivery and installation.

      Brand: DEHN
      Type: DG SE CI WE 440 FM
      Part No.: 952 923

      or equivalent.
      Installation Instructions
      Certificates
      71-101107
      CE_DG_SE_CI_WE_440_FM
      CAD-Data for registered Users
      972125.stp
      972125.igs
      972125.jt
      972125.dwg
      952930m_E.dxf

Accessories

Varistor-based Protection Module for DEHNguard SE CI (WE)


Specifications

Type
Part No.
Max. continuous operating voltage (d.c.) (UC)
Rated varistor voltage (a.c.) (Umov)
Weight
GTIN
PU

Earthing Clip for 1.5-module Enclosures, single-phase, three-pole

Earthing clip for connecting the earth terminal of e.g. three SPDs with 1.5-module enclosure to earth, with terminal.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Dimensions
Terminal
Weight
GTIN
PU
  • EB 1 3 1.5
  • 900 418
  • 34 x 85 x 28 mm
  • up to 25 mm2
  • 49 g
  • 4013364159884
  • 1 pc(s)
  • Specifications (PDF)
  • More
    • Further Pictures
      Further Information
      Product Specifications (Text)

      Back

      Three-pole EB 1 3 1.5 earthing clip
      Earthing clip for connecting the earth terminal of e.g. three
      SPDs with 1.5-module enclosure and terminal to earth
      Single-phase, three-pole
      Terminal up to 25 mm2
      Dimensions: (31 x 85 x 28) mm

      delivery and installation.

      Brand: DEHN
      Type: EB 1 3 1.5
      Part No.: 900 418

      or equivalent.