DEHNguard® SE H ... FM

Single-pole Surge Arrester with "Lifetime Indication“

Single-pole surge arrester with integrated "Lifetime Indication" early warning system. For protecting low-voltage consumer's installations from surges. For installation in conformity with the lightning protection zone concept at the boundaries from 0B– 1 and higher.
  • Universal surge arrester comprising a base part and a plug-in protection module
  • Prewired single-pole surge arrester with clear "Lifetime Indication“
  • Three-step “Lifetime Indication“ (green-yellow-red) linked with remote signalling contact
  • High discharge capacity Imax up to 65 kA (8/20 μs)
  • Prompts the user in time <YELLOW> to replace the protection module in case of imminent arrester overload; early warning system
  • The arrester is fully operational until the protection module is replaced and is thus suited for use in condition monitoring systems
  • Energy coordination with other arresters of the Red/Line product family
  • Easy replacement of protection modules without tools due to module locking system with module release button

Version

DEHNguard SE H LI ... FM: Pluggable single-pole surge arrester with three-step early warning system (green-yellow-red) comprising a base part and a plug-in protection module; with remote signalling contact for monitoring unit (floating changeover contact)
DEHNguard SE H 1000 FM: Pluggable single-pole surge arrester with a high discharge capacity comprising a base part and a plug-in protection module; with remote signalling contact for monitoring unit (floating changeover contact)
DEHNguard SE H 1000 VA FM: Pluggable single-pole surge arrester with a high discharge capacity and a varistor connected in series with a spark gap comprising a base part and a plug-in protection module; with remote signalling contact for monitoring unit (floating changeover contact)

Details

The single-pole type 2 DEHNguard SE H LI … FM surge arresters with a functional Red/Line design provide a high degree of safety and comfort and ensure maximum availability of electrical installations.
The three-step "Lifetime Indication“ provides reliable information on the operating state of the surge protective device. The yellow indication shows that a certain energy has pre-damaged the arrester during its lifetime. Moreover, the remote signalling contact is activated so that the arrester can be easily integrated condition monitoring systems. During this yellow indication, the connected electrical equipment is still protected against surges since the protection module is fully operational. Now the protection module can be replaced in time (without disconnecting the mains voltage and removing the distribution board cover) – Before further energies overload the arrester and the installation is unprotected! Thus, the lifetime between commissioning (green indication) and disconnection (red indication) of DEHNguard SE H LI … FM consists of two periods: After typically 70% of the total nominal discharge current load, the indication changes from green to yellow. Consequently, about 30% of the total load capacity remain for the yellow phase during which the surge protective device is fully operational. This makes this indication an ideal early warning system!
The single-pole devices are available for voltages from 275 V to 1000 V a.c. and are thus universally applicable. In addition, the product family has a high discharge capacity Imax up to 65 kA (8/20 µs) and is thus more powerful across all voltage levels than conventional type 2 arresters.
The devices feature the special modular Red/Line family design with a width of 1.5 modules to implement the variety of functions. They can be used as a single device or in combination with other devices and always provide adequate protection. All necessary components such as earthing clips EB 1 ... 1.5 with modular dimensions of 1.5 modules are available as accessory to ensure the correct connection for the relevant system configuration as per IEC 60364-5-53.

Consequently, the intelligent DEHNguard SE H LI … FM family allows to protect installations which require maximum availability such as data centres, power plants or wind turbines against surges. Planned maintenance for type 2 surge protective devices can be easily and efficiently performed in all low-voltage installations.
Both the three-step monitoring unit of the surge protective devices and the coded plug-in protection module types underline the high degree of safety of the arrester and damage caused by installing an incorrect module can be virtually excluded.
In addition to the standard three-step visual indication, the arresters feature a three-pole remote signalling terminal. With its floating changeover contact, the remote signal can be used as a break or make contact according to the particular circuit concept.

The DEHNguard SE H 1000 FM type is a special arrester of the DEHNguard ... H ... series. Compared to the LI devices, whose designation includes the abbreviation "LI", it features a two-step visual indication which changes from green to red as soon as the max. load capacity of the arrester is reached and activates the floating changeover contact.

The DEHNguard SE H 1000 VA FM type is a particularly powerful type 2 arrester designed for high voltages and discharge currents. Due to the high nominal voltage and the series connection of a varistor and a gas discharge tube, it is ideally suited for wind turbines (rotor and inverter), but also for other applications such as PV systems, railway systems or cable cars with high voltages where absence of leakage current is required.

Models

DEHNguard SE H LI ... FM

DEHNguard SE H 1000 FM

DEHNguard SE H 1000 VA FM

DEHNguard SE H LI ... FM

Basic circuit diagram DG SE H LI ... FMDimension drawing DG SE H LI ... FM

Pluggable single-pole surge arrester with three-step early warning system (green-yellow-red) comprising a base part and a plug-in protection module; with floating remote signalling contact.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) (UC)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Voltage protection level (UP)
Voltage protection level at 5 kA (UP)
Response time (tA)
Max. mains-side overcurrent protection
Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR)
Temporary overvoltage (TOV) (UT) – Characteristic
Temporary overvoltage (TOV) (UT) – Characteristic
Operating temperature range (TU)
Operating state / fault indication
Remote signalling
Number of ports
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Place of installation
Degree of protection
Capacity
Type of remote signalling contact
Switching capacity (a.c.)
Switching capacity (d.c.)
Cross-sectional area for remote signalling terminals
Weight
GTIN
PU
Part No.
  • DG SE H LI 275 FM
  • 952 930
  • type 2 / class II
  • type 2 + type 3
  • 230 V (50 / 60 Hz)
  • 275 V (50 / 60 Hz)
  • 30 kA
  • 65 kA
  • ≤ 1.5 kV
  • ≤ 1 kV
  • ≤ 25 ns
  • 125 A gG
  • 50 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • -40 °C ... +80 °C
  • green / yellow / red
  • activated in case of yellow indication
  • 1
  • 1.5 mm2 solid / flexible
  • 35 mm2 stranded / 25 mm2 flexible
  • 35 mm DIN rails acc. to EN 60715
  • thermoplastic, red, UL 94 V-0
  • indoor installation
  • IP20
  • 1.5 module(s), DIN 43880
  • changeover contact
  • 250 V / 0.5 A
  • 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
  • max. 1.5 mm2 solid / flexible
  • 171 g
  • 4013364158559
  • 1 pc(s)
  • 952 930
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram DG SE H LI 275 FM
      open PDF
      Dimension drawing DG SE H LI 275 FM
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DEHNguard SE H LI 275 FM surge arrester
      Modular and pluggable single-pole surge arrester 
      with three-step indication (green-yellow-red) 
      (early warning system) and remote signalling contact,
      width: 1.5 modules  
      Type 2 SPD according to EN 61643-11
      Max. continuous operating voltage: 	275 V a.c.
      Voltage protection level :		<= 1.5 kV
      Nominal discharge current: 		30 kA
      Short-circuit strength: 		50 kArms
      Energy-coordinated according to IEC 62305-4 
      with arresters of the Red/Line series
      Monitoring: Lifetime indication with integrated
      pre-warning phase (yellow) in case of imminent arrester overload 
      Fully functional even during the pre-warning phase 

      delivery and installation.

      Brand: DEHN
      Type: DG SE H LI 275 FM
      Part No.: 952 930

      or equivalent.
      Installation Instructions
      Certificates
      CE_DG_SE_H_LI_275_FM
      CAD-Data for registered Users
      972125.stp
      972125.igs
      972125.jt
      972125.dwg
      952930m_E.dxf
  • DG SE H LI 1000 FM
  • 952 937
  • type 2 / class II
  • type 2 + type 3
  • 690 V (50 / 60 Hz)
  • 1000 V (50 / 60 Hz)
  • 20 kA
  • 40 kA
  • ≤ 4.5 kV
  • ≤ 3.5 kV
  • ≤ 25 ns
  • 100 A gG
  • 25 kArms
  • 1205 V / 5 sec. – withstand
  • 1320 V / 120 min. – safe failure
  • -40 °C ... +80 °C
  • green / yellow / red
  • activated in case of yellow indication
  • 1
  • 1.5 mm2 solid / flexible
  • 35 mm2 stranded / 25 mm2 flexible
  • 35 mm DIN rails acc. to EN 60715
  • thermoplastic, red, UL 94 V-0
  • indoor installation
  • IP20
  • 1.5 module(s), DIN 43880
  • changeover contact
  • 250 V / 0.5 A
  • 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
  • max. 1.5 mm2 solid / flexible
  • 207 g
  • 4013364158603
  • 1 pc(s)
  • 952 937
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram DG SE H LI 1000 FM
      open PDF
      Dimension drawing DG SE H LI 1000 FM
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DEHNguard SE H LI 1000 FM surge arrester
      Modular and pluggable single-pole surge arrester 
      with three-step indication (green-yellow-red) 
      (early warning system) and remote signalling contact,
      width: 1.5 modules 
      Type 2 SPD according to EN 61643-11
      Max. continuous operating voltage: 1000 V a.c.
      Voltage protection level : <= 4.5 kV
      Nominal discharge current: 2	30 kA
      Short-circuit strength: 25 kArms
      Energy-coordinated according to IEC 62305-4 
      with arresters of the Red/Line series
      Monitoring: Lifetime indication with integrated
      pre-warning phase (yellow) in case of imminent arrester overload 
      Fully functional even during the pre-warning phase 
      Coded protection module

      delivery and installation.

      Brand: DEHN
      Type: DG SE H LI 1000 FM
      Part No.: 952 937

      or equivalent.
      Installation Instructions
      Certificates
      CE_DG_SE_H_LI_1000_FM
      CAD-Data for registered Users
      972125.stp
      972125.igs
      972125.jt
      972125.dwg
      952930m_E.dxf

DEHNguard SE H 1000 FM

Basic circuit diagram DG SE H 1000 FMDimension drawing DG SE H 1000 FM

Pluggable single-pole surge arrester comprising a base part and a plug-in protection module; with floating remote signalling contact.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) (UC)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Voltage protection level (UP)
Voltage protection level at 5 kA (UP)
Response time (tA)
Max. mains-side overcurrent protection
Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR)
Temporary overvoltage (TOV) (UT) – Characteristic
Temporary overvoltage (TOV) (UT) – Characteristic
Operating temperature range (TU)
Operating state / fault indication
Number of ports
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Place of installation
Degree of protection
Capacity
Type of remote signalling contact
Switching capacity (a.c.)
Switching capacity (d.c.)
Cross-sectional area for remote signalling terminals
Weight
GTIN
PU
Part No.
  • DG SE H 1000 FM
  • 952 938
  • type 2 / class II
  • type 2 + type 3
  • 690 V (50 / 60 Hz)
  • 1000 V (50 / 60 Hz)
  • 20 kA
  • 40 kA
  • ≤ 4.5 kV
  • ≤ 3.5 kV
  • ≤ 25 ns
  • 100 A gG
  • 25 kArms
  • 1205 V / 5 sec. – withstand
  • 1320 V / 120 min. – safe failure
  • -40 °C ... +80 °C
  • green / red
  • 1
  • 1.5 mm2 solid / flexible
  • 35 mm2 stranded / 25 mm2 flexible
  • 35 mm DIN rails acc. to EN 60715
  • thermoplastic, red, UL 94 V-0
  • indoor installation
  • IP20
  • 1.5 module(s), DIN 43880
  • changeover contact
  • 250 V / 0.5 A
  • 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
  • max. 1.5 mm2 solid / flexible
  • 207 g
  • 4013364264014
  • 1 pc(s)
  • 952 938
  • Specifications (PDF)
  • More

DEHNguard SE H 1000 VA FM

Basic circuit diagram DG SE H 1000 VA FMDimension drawing DG SE H 1000 VA FM

Pluggable single-pole surge arrester comprising a base part and a plug-in protection module; with floating remote signalling contact. Series connection of a varistor and a gas discharge tube.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) (UC)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Voltage protection level (UP)
Response time (tA)
Max. mains-side overcurrent protection
Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR)
Temporary overvoltage (TOV) (UT) – Characteristic
Temporary overvoltage (TOV) (UT) – Characteristic
Operating temperature range (TU)
Operating state / fault indication
Number of ports
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Place of installation
Degree of protection
Capacity
Approvals
Type of remote signalling contact
Switching capacity (a.c.)
Switching capacity (d.c.)
Cross-sectional area for remote signalling terminals
Supplementary data:
– Sparkover voltage gas discharge tube (Uagmin)
Weight
GTIN
PU
Part No.
  • DG SE H 1000 VA FM
  • 952 940
  • type 2 / class II
  • type 2 + type 3
  • 690 V (50 / 60 Hz)
  • 1000 V (50 / 60 Hz)
  • 15 kA
  • 40 kA
  • ≤ 5 kV
  • ≤ 25 ns
  • 100 A gG
  • 25 kArms
  • 1550 V / 5 sec. – withstand
  • 1320 V / 120 min. – withstand
  • -40 °C ... +80 °C
  • green / red
  • 1
  • 1.5 mm2 solid / flexible
  • 35 mm2 stranded / 25 mm2 flexible
  • 35 mm DIN rails acc. to EN 60715
  • thermoplastic, red, UL 94 V-0
  • indoor installation
  • IP20
  • 1.5 module(s), DIN 43880
  • UL
  • changeover contact
  • 250 V / 0.5 A
  • 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
  • max. 1.5 mm2 solid / flexible
  • ---------------------------------------
  • 2200 V
  • 207 g
  • 4013364308329
  • 1 pc(s)
  • 952 940
  • Specifications (PDF)
  • More

Accessories

Varistor-based Protection Module for DEHNguard SE H ... FM


Specifications

Type
Part No.
Max. continuous operating voltage (d.c.) (UC)
Weight
GTIN
PU
  • DG MOD E H LI 275
  • 952 900
  • 275 V
  • 80 g
  • 4013364158801
  • 1 pc(s)
  • Specifications (PDF)
  • More
    • Further Pictures
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DG MOD E H LI 275 varistor-based protection module
      Pluggable protection module for DEHNguard 
      SE H LI 275 FM
      with three-step early warning system 
      Type 2 SPD according to EN 61643-11 
      Heavy-duty varistor technology
      Max. continuous operating voltage: 275 V d.c.
      Nominal discharge current: 30 kA
      Lifetime indication

      delivery and installation.

      Brand: DEHN
      Type: DG MOD E H LI 275
      Part No.: 952 900

      or equivalent.
      Installation Instructions
      Certificates
      CE_DG_SE_H_LI_275_FM
  • DG MOD E H LI 1000
  • 952 907
  • 1000 V
  • 112 g
  • 4013364158856
  • 1 pc(s)
  • Specifications (PDF)
  • More
    • Further Pictures
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DG MOD E H LI 1000 varistor-based protection module
      Pluggable protection module for DEHNguard 
      SE H LI 1000 FM
      with three-step early warning system 
      Type 2 SPD according to EN 61643-11 
      Heavy-duty varistor technology
      Max. continuous operating voltage: 1000 V d.c.
      Nominal discharge current: 20 kA
      Coded protection module

      delivery and installation.

      Brand: DEHN
      Type: DG MOD E H LI 1000
      Part No.: 952 907

      or equivalent.
      Installation Instructions
      Certificates
      CE_DG_SE_H_LI_1000_FM

Earthing Clip for 1.5-module Enclosures, single-phase, two-pole

Earthing clip for connecting the earth terminal of e.g. two SPDs with 1.5-module enclosure to earth, with terminal.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Dimensions
Terminal
Weight
GTIN
PU
  • EB 1 2 1.5
  • 900 460
  • 34 x 60 x 28 mm
  • up to 25 mm2
  • 37 g
  • 4013364244146
  • 1 pc(s)
  • Specifications (PDF)
  • More
    • Further Pictures
      Further Information
      Product Specifications (Text)

      Back

      Two-pole EB 1 2 1.5 earthing clip
      Earthing clip for connecting the earth terminal of e.g. two
      SPDs with 1.5-module enclosure and terminal to earth
      Single-phase, two-pole
      Terminal up to 25 mm2
      Dimensions:	(31 x 60 x 28) mm

      delivery and installation.

      Brand: DEHN
      Type: EB 1 2 1.5
      Part No.: 900 460

      or equivalent.

Earthing Clip for 1.5-module Enclosures, single-phase, three-pole

Earthing clip for connecting the earth terminal of e.g. three SPDs with 1.5-module enclosure to earth, with terminal.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Dimensions
Terminal
Weight
GTIN
PU
  • EB 1 3 1.5
  • 900 418
  • 34 x 85 x 28 mm
  • up to 25 mm2
  • 49 g
  • 4013364159884
  • 1 pc(s)
  • Specifications (PDF)
  • More
    • Further Pictures
      Further Information
      Product Specifications (Text)

      Back

      Three-pole EB 1 3 1.5 earthing clip
      Earthing clip for connecting the earth terminal of e.g. three
      SPDs with 1.5-module enclosure and terminal to earth
      Single-phase, three-pole
      Terminal up to 25 mm2
      Dimensions: (31 x 85 x 28) mm

      delivery and installation.

      Brand: DEHN
      Type: EB 1 3 1.5
      Part No.: 900 418

      or equivalent.

Earthing Clip for 1.5-module Enclosures, single-phase, four-pole

Earthing clip for connecting the earth terminal of e.g. four SPDs with 1.5-module enclosure to earth, with terminal.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Dimensions
Terminal
Weight
GTIN
PU
  • EB 1 4 1.5
  • 900 429
  • 34 x 112 x 28 mm
  • up to 25 mm2
  • 59 g
  • 4013364159891
  • 1 pc(s)
  • Specifications (PDF)
  • More
    • Further Pictures
      Further Information
      Product Specifications (Text)

      Back

      Four-pole EB 1 4 1.5 3 earthing clip
      Earthing clip for connecting the earth terminal of e.g. four
      SPDs with 1.5-module enclosure to earth; with multifunctional terminal
      Single-phase, four-pole
      Terminal up to 25 mm2
      Dimensions: (31 x 85 x 28) mm

      delivery and installation.

      Brand: DEHN
      Type: EB 1 4 1.5
      Part No.: 900 429

      or equivalent.