STC Module

Surge arrester for earthed socket outlets

For protecting electronic devices against surges. For use with standard earthed socket outlets. For installation in conformity with the lightning protection zone concept at the boundaries from 1 – 2 and higher.
  • Two-pole surge arrester with monitoring device and disconnector
  • Enhanced safety due to fault-proof Y protective circuit
  • Acoustic fault indication
  • For installation in standard earthed socket outlets
  • Independent of the socket outlet design
  • Plastic snap-on retaining ring for easy installation in already mounted socket outlets

Version

STC 230: Snap-on module for standard earthed socket outlets

Details

The well received two-pole STC surge arrester can be fitted inconspicuously on the rear side of many standard earthed socket outlets. The STC surge protection module thus adapts to every type of socket outlet. The plastic snap-on retaining ring allows easy installation even in already mounted earthed socket outlets. In addition to a thermal disconnector, the protective device features an acoustic fault indication. As the surge protection module is installed in parallel to the socket outlet, the power supply of the connected loads remains uninterrupted, even if the surge arrester is overloaded.

Models

STC 230

STC 230

Basic circuit diagram STC 230Dimension drawing STC 230

Two-pole surge arrester for single-phase 230 V TT and TN systems is snapped on earthed socket outlets.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) (UC)
Nominal discharge current (8/20 µs) (In)
Total discharge current (8/20 µs) [L+N-PE] (Itotal)
Combination wave (UOC)
Combination wave [L+N-PE] (UOC total)
Voltage protection level [L-N] / [L/N-PE] (UP)
Response time [L-N] (tA)
Response time [L/N-PE] (tA)
Max. mains-side overcurrent protection
Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR)
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L/N-PE] (UT) – Characteristic
Temporary overvoltage (TOV) [L/N-PE] (UT) – Characteristic
Temporary overvoltage (TOV) [L+N-PE] (UT) – Characteristic
Operating temperature range (TU)
Fault indication
Number of ports
Terminal wires
For mounting on
Enclosure material
Place of installation
Degree of protection of installed device
Dimensions
Weight
GTIN
PU
Part No.
  • STC 230
  • 924 350
  • type 3 / class III
  • 230 V (50 / 60 Hz)
  • 255 V (50 / 60 Hz)
  • 3 kA
  • 5 kA
  • 6 kV
  • 10 kV
  • ≤ 1250 / ≤ 1500 V
  • ≤ 25 ns
  • ≤ 100 ns
  • B 16 A
  • 1 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • 335 V / 120 min. – withstand
  • 440 V / 5 sec. – withstand
  • 1200 V + UREF / 200 ms – safe failure
  • -25 °C ... +40 °C
  • acoustic signal on
  • 1
  • 1 mm2, 120 mm long
  • standard earthed socket outlets
  • thermoplastic, red, UL 94 V-2
  • indoor installation
  • IP 20
  • 54 x 54 x 32 mm
  • 34 g
  • 4013364076709
  • 1 pc(s)
  • 924 350
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram STC 230
      open PDF
      Dimension drawing STC 230
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      Two-pole STC 230 surge arrester module
      Two-pole surge arrester for 
      standard Schuko socket outlets
      Can be snapped onto existing socket outlets
      Type 3 SPD according to EN 61643-11
      No interruption of the supply circuit in case of fault
      Acoustic fault indication
      Max. continuous operating voltage: 255 V a.c. 
      Voltage protection level: <= 1.5 kV 
      Total discharge current: 		5 kA
      Max. mains-side overcurrent protection: 16 A gG or B 16 A
      Energy-coordinated according to IEC 62305-4 with arresters 
      of the Red/Line series

      delivery and installation.

      Brand: DEHN
      Type: STC 230
      Part No.: 924 350

      or equivalent.
      Installation Instructions
      Certificates
      CE_STC_230
      CAD-Data for registered Users
      924350m_E.dxf