DEHNcap/IT Interface Test Unit

Nominal Voltages up to 45 kV / 50 Hz

DEHNcap/IT interface test unit allows to carry out maintenance tests on coupling systems of switchgear installations according to IEC/EN 61243-5 (DIN VDE 0682-415).
    Easy and safe testing
  • User-friendly
  • Easy handling

Details

Self-testing element
The DEHNcap/IT interface test unit has an integrated self-testing element. By simply pressing the test button, the electronic circuit is tested for correct operation. The self-test is automatically performed as soon as the indicator is switched on. The interface test unit is only operational if the test button is pressed i.e. the function test was performed successfully.

Models

DEHNcap/IT-LRM

DEHNcap/IT-LRM


Specifications

Type
Part No.
Nominal voltage (UN)
Dimensions
Plug spacing
Type of plug
Input impedance (LRM system)
Test threshold
Standard
Temperature range
Type of device
Use
Indication
Type of system
Self-testing element
Weight
GTIN
PU
Part No.
  • SPG DCA IT LRM
  • 767 122
  • 1 ... 45 kV
  • 120 x 60 x 25 mm
  • 14 mm
  • 2 multilam plugs (Ø4 mm)
  • 2 MOhms
  • 3.2 µA
  • EN/IEC 61243-5 (DIN VDE 0682-415)
  • –25 °C ... +55 °C
  • Interface test unit
  • Active indicator for maintenance test of coupling systems
  • Visual
  • LRM
  • Yes
  • 185 g
  • 4013364074385
  • 1 pc(s)
  • 767 122
  • Specifications (PDF)
  • More

Accessories

HR-LRM Measuring Adapter

For electrical and mechanical adaptation of HR (HO) systems to LRM systems. Used as a measuring impedance with XC = 36 megohms for maintenance tests of HR coupling systems (with suitable μA meter).

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Dimensions
Plug spacing
Socket spacing
Weight
GTIN
PU

LR-LRM Measuring Adapter

For mechanical adaptation of LR (NO) systems to LRM systems.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Dimensions
Plug spacing
Socket spacing
Weight
GTIN
PU

XC-LRM Measuring Impedance

Used as a measuring impedance with XC = 2 megohms for maintenance tests of LRM coupling systems (with suitable μA meter).

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Dimensions
Plug spacing
Socket spacing
Weight
GTIN
PU

Plastic Case


Specifications

Type
Part No.
Colour
Dimensions
Weight
GTIN
PU

Plastic Case

With foam padding.
Max. capacity:
1 DEHNcap/PC
2 DEHNcap/A or IT
2 Test adapters
2 DEHNcap/P
1 DEHNcap/P test unit

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Colour
Dimensions
Weight
GTIN
PU