DEHNcap/P Voltage Indicator

Nominal Voltages up to 45 kV / 50 Hz

DEHNcap/P passive voltage indicator used in an encapsulated switchgear installation.
    Easy verification of isolation from supply voltage
  • Cost-effective

Details

Test for correct operation
EN 50110-1 (DIN VDE 0105-100) requires that voltage indicators be tested for correct operation shortly before and after use.
Passive indicators without self-testing element must be tested for correct operation by plugging them into test sockets connected to operating voltage or into a test unit (DEHNcap/P test unit).

Models

DEHNcap/P-HR

DEHNcap/P-LRM

DEHNcap/P-HR


Specifications

Type
Part No.
Nominal voltage (UN)
Frequency
Dimensions
Plug spacing
Indication threshold (HR system)
Input impedance (HR system)
Standard
Temperature range
Degree of protection
Type of device
Use
Indication
Type of system
Self-testing element
Weight
GTIN
PU
Part No.
  • SAG DCA P HR GA
  • 767 101
  • 1 ... 45 kV
  • 50 Hz
  • 40 x 48 x 35 mm
  • 19 mm
  • 90 V
  • 36 MOhms
  • EN/IEC 61243-5 (DIN VDE 0682-415)
  • –25 °C ... +55 °C
  • IP 66
  • Voltage indicator
  • Can also be used as permanent voltage indicator
  • Visual
  • HR
  • No
  • 60 g
  • 4013364069541
  • 1 pc(s)
  • 767 101
  • Specifications (PDF)
  • More

DEHNcap/P-LRM


Specifications

Type
Part No.
Nominal voltage (UN)
Frequency
Dimensions
Plug spacing
Indication threshold (LRM system)
Input impedance (LRM system)
Standard
Temperature range
Degree of protection
Type of device
Use
Indication
Type of system
Weight
GTIN
PU
Part No.
  • SAG DCA P LRM GA
  • 767 102
  • 1 ... 45 kV
  • 50 Hz
  • 40 x 48 x 35 mm
  • 14 mm
  • 5 V
  • 2 MOhms
  • EN/IEC 61243-5 (DIN VDE 0682-415)
  • –25 °C ... +55 °C
  • IP 66
  • Voltage indicator
  • Can also be used as permanent voltage indicator
  • Visual
  • LRM
  • 62 g
  • 4013364074064
  • 1 pc(s)
  • 767 102
  • Specifications (PDF)
  • More

Accessories

Test Unit for DEHNcap/P


Specifications

Type
Part No.
Nominal voltage (UN)
Frequency
Test voltage (HR system)
Socket spacing (HR system)
Test voltage (LRM system)
Socket spacing (LRM system)
Nominal capacity
Max. short-circuit current at the test socket
Dimensions
Temperature range during installation
Application
Weight
GTIN
PU
Part No.

Plastic Case

With foam padding.
Max. capacity:
1 DEHNcap/PC
2 DEHNcap/A or IT
2 Test adapters
2 DEHNcap/P
1 DEHNcap/P test unit

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Colour
Dimensions
Weight
GTIN
PU