Rooftop systems: Buildings without external lightning protection

What happens if a photovoltaic system is newly or subsequently installed … does the new system require lightning protection measures for the entire building?

Normative requirements and notes:

If no external lightning protection system is installed (and this is not required according to the risk analysis in conformity with IEC 62305-2), Supplement 5 to DIN EN 62305-3 recommends to use a type 2 surge protective device on the d.c. and a.c. side to protect PV systems from inductive and conducted interference. Moreover, the data interfaces are to be protected by means of adequate surge arresters.

Comprehensive protection

The d.c. and a.c. side as well as the data interfaces are protected and equipotential bonding is established to ensure comprehensive protection of a rooftop system on a building without lightning protection system.

 