BLITZDUCTOR® XT Ex (i) – Protection Modules

Surge Arrester

Pluggable and universal multipole surge arrester for use in intrinsically safe systems with integrated LifeCheck monitoring function.
    Surge arrester for intrinsically safe measuring circuits and bus systems
  • Maximum discharge capacity for two-pole, three-pole or four-pole interfaces
  • Low voltage protection level, capable of protecting terminal equipment
  • Wide range of approvals: ATEX, IECEx, CSA Hazloc
  • Arrester consists of a protection module and a base part
  • Easy replacement of protection modules without force
  • All protection components are integrated in the protection module
  • Arrester with integrated LifeCheck for preventive arrester monitoring
  • Functional and appealing design
  • DIN rail mounted arrester with integrated earthing
  • Minimum space requirements, two pairs over a width of 12 mm
  • Vibration and shock-tested for safe operation

Description

BLITZDUCTOR XT EX is a pluggable and universal four-pole DIN rail mounted surge arrester designed for the most stringent requirements on the availability of intrinsically safe measuring and control circuits and bus systems.
Regarding intrinsic safety, the arrester is considered unearthed and its self-inductance and self-capacitance are negligibly small. The low-impedance arrester design ensures a high impulse current discharge capacity (at least 10x) and a low voltage protection level.
LifeCheck allows quick and easy arrester testing, however, the protection modules may only be read by the hand-held DRC LC reader in non-explosive atmospheres.
Integrated in the protection modules, LifeCheck permanently monitors the operating state of the arrester. Like an early warning system, LifeCheck detects imminent electrical or thermal overload of the protection components. The LifeCheck status can be read in a second by the hand-held DEHNrecord LC reader via non-contact RFID technology. Moreover, the date of the last test of the protection module can be displayed and saved. Stationary installed, a condition monitoring system allows condition-based maintenance of 10 BXT arresters.
The arrester provides protection against vibration effects and shock up to a 30-fold acceleration of gravity. The function-optimised arrester design allows quick and easy replacement of protection modules which house all relevant protection elements.
The protection module and base part must be ordered separately!

Detail 1

Two-part design comprising a universal base part and an application-specific protection module.

Detail 2

The module locking mechanism ensures that the module is vibration-proof and protected against polarity reversal.

Detail 3

All protection elements are integrated in the plug-in module and are monitored by means of LifeCheck.

Detail 4

Prewired surge arrester unit ITAK EXI BXT 24.

Models

BXT ML4 BD EX 24

BXT ML2 BD S EX 24

BXT ML4 BC EX 24

BXT ML2 BD HF EX 6

BXT M2 BD S EX 24

BXT ML4 BD EX 24

Basic circuit diagramBXT ML4 BD EXDimension drawing BXT ML4 BD EX

Space-saving LifeCheck-equipped surge arrester module for protecting two pairs in intrinsically safe measuring circuits and bus systems, meets FISCO requirements. ATEX. Insulation strength > 500 V line-earth.
If LifeCheck detects thermal or electrical overload, the arrester has to be replaced. This status is indicated contactlessly by DEHNrecord LC / SCM / MCM.


Specifications

Type
Part No.
SPD class
SPD monitoring
Nominal voltage (UN)
Max. continuous operating voltage (d.c.) (Uc)
Max. continuous operating voltage (a.c.) (Uc)
Max. input voltage acc. to EN 60079-11 (Ui)
Max. input current acc. to EN 60079-11 (Ii)
D1 Total lightning impulse current (10/350 µs) (Iimp)
D1 Lightning impulse current (10/350 µs) per line (Iimp)
C2 Total nominal discharge current (8/20 µs) (In)
C2 Nominal discharge current (8/20 µs) per line (In)
Voltage protection level line-line for Iimp D1 (Up)
Voltage protection level line-PG for Iimp D1 (Up)
Voltage protection level line-line for In C2 (Up)
Voltage protection level line-PG for In C2 (Up)
Voltage protection level line-line at 1 kV/µs C3 (Up)
Voltage protection level line-PG at 1 kV/µs C3 (Up)
Series resistance per line
Cut-off frequency line-line (fG)
Capacitance line-line (C)
Capacitance line-PG (C)
Operating temperature range (TU)
Degree of protection (with plugged-in protection module)
Plugs into
Earthing via
Enclosure material
Colour
Test standards
Approvals *)
SIL classification
ATEX approvals (1)
ATEX approvals (2)
IECEx approvals (1)
IECEx approvals (2)
CSA & USA Hazloc approvals (1)
CSA & USA Hazloc approvals (2)
Inmetro approvals
Weight
GTIN
PU
Part No.
*) For more detailed information, please visit www.dehn-international.com.
  • BXT ML4 BD EX 24
  • 920 381
  • T
  • LifeCheck
  • 24 V
  • 33 V
  • 23 V
  • 30 V
  • 0.5 A
  • 4 kA
  • 1 kA
  • 20 kA
  • 5 kA
  • ≤ 50 V
  • ≤ 1300 V
  • ≤ 52 V
  • ≤ 1400 V
  • ≤ 45 V
  • ≤ 1100 V
  • 1.0 ohm
  • 7.7 MHz
  • ≤ 0.8 nF
  • ≤ 16 pF
  • -40 °C ... +80 °C
  • IP 20
  • base part
  • base part
  • polyamide PA 6.6
  • blue
  • IEC 61643-21 / EN 61643-21, UL 497B
  • CSA, EACEx, ATEX, IECEx, CSA & USA Hazloc, SIL, Inmetro
  • up to SIL3 *)
  • KEMA 06ATEX0274 X: II 2 (1) G Ex ia [ia Ga] IIC T4 ... T6 Gb
  • KEMA 06ATEX0274 X: II 2 G Ex ib IIC T4 ... T6 Gb
  • DEK 11.0078X: Ex ia [ia Ga] IIC T4 ... T6 Gb
  • DEK 11.0078X: Ex ib IIC T4 ... T6 Gb
  • 70000011: Class I Div. 1; Class I Zone 1
  • 70000011: Ex ia [ia] IIC T4 ... T6
  • TÜV 17.0697 X: Ex ia [ia Ga] IIC T6 ... T4 Gb
  • 23 g
  • 4013364109025
  • 1 pc(s)
  • 920 381
  • Specifications (PDF)
  • More

BXT ML2 BD S EX 24

Basic circuit diagramBXT ML2 BD S EXDimension drawing BXT ML2 BD S EX

Space-saving LifeCheck-equipped surge arrester module for protecting one pair in intrinsically safe measuring circuits and bus systems, direct or indirect shield earthing. Insulation strength > 500 V line-earth.
If LifeCheck detects thermal or electrical overload, the arrester has to be replaced. This status is indicated contactlessly by DEHNrecord LC / SCM / MCM.


Specifications

Type
Part No.
SPD class
SPD monitoring
Nominal voltage (UN)
Max. continuous operating voltage (d.c.) (Uc)
Max. continuous operating voltage (a.c.) (Uc)
Max. input voltage acc. to EN 60079-11 (Ui)
Max. input current acc. to EN 60079-11 (Ii)
D1 Total lightning impulse current (10/350 µs) (Iimp)
D1 Lightning impulse current (10/350 µs) per line (Iimp)
C2 Total nominal discharge current (8/20 µs) (In)
C2 Nominal discharge current (8/20 µs) per line (In)
Voltage protection level line-line for Iimp D1 (Up)
Voltage protection level line-PG for Iimp D1 (Up)
Voltage protection level line-line for In C2 (Up)
Voltage protection level line-PG for In C2 (Up)
Voltage protection level line-line at 1 kV/µs C3 (Up)
Voltage protection level line-PG at 1 kV/µs C3 (Up)
Series resistance per line
Cut-off frequency line-line (fG)
Capacitance line-line (C)
Capacitance line-PG (C)
Operating temperature range (TU)
Degree of protection (with plugged-in protection module)
Plugs into
Earthing via
Enclosure material
Colour
Test standards
Approvals *)
ATEX approvals (1)
ATEX approvals (2)
IECEx approvals (1)
IECEx approvals (2)
CSA & USA Hazloc approvals (1)
CSA & USA Hazloc approvals (2)
Inmetro approvals
Weight
GTIN
PU
Part No.
*) For details see: www.dehn-international.com
  • BXT ML2 BD S EX 24
  • 920 280
  • T
  • LifeCheck
  • 24 V
  • 33 V
  • 23.3 V
  • 30 V
  • 0.5 A
  • 4 kA
  • 1 kA
  • 10 kA
  • 5 kA
  • ≤ 50 V
  • ≤ 1300 V
  • ≤ 52 V
  • ≤ 1400 V
  • ≤ 45 V
  • ≤ 1100 V
  • 1.0 ohm
  • 6 MHz
  • ≤ 1.0 nF
  • ≤ 16 pF
  • -40 °C ... +80 °C
  • IP 20
  • base part
  • base part
  • polyamide PA 6.6
  • blue
  • IEC 61643-21 / EN 61643-21
  • EACEx, ATEX, IECEx, CSA & USA Hazloc, SIL, Inmetro
  • KEMA 06ATEX0274 X: II 2 (1) G Ex ia [ia Ga] IIC T4 ... T6 Gb
  • KEMA 06ATEX0274 X: II 2 G Ex ib IIC T4 ... T6 Gb
  • DEK 11.0078X: Ex ia [ia Ga] IIC T4 ... T6 Gb
  • DEK 11.0078X: Ex ib IIC T4 ... T6 Gb
  • 70000011: Class I Div. 1; Class I Zone 1
  • 70000011: Ex ia [ia] IIC T4 ... T6
  • TÜV 17.0697 X: Ex ia [ia Ga] IIC T6 ... T4 Gb
  • 22 g
  • 4013364142138
  • 1 pc(s)
  • 920 280
  • Specifications (PDF)
  • More

BXT ML4 BC EX 24

Basic circuit diagram BXT ML4 BC EXDimension drawing BXT ML4 BC EX

Space-saving LifeCheck-equipped surge arrester module for protecting up to four unearthed single lines sharing a common reference potential in intrinsically safe measuring circuits, meets FISCO requirements. ATEX. Insulation strength > 500 V line-earth.
If LifeCheck detects thermal or electrical overload, the arrester has to be replaced. This status is indicated contactlessly by DEHNrecord LC / SCM / MCM.


Specifications

Type
Part No.
SPD class
SPD monitoring
Nominal voltage (UN)
Max. continuous operating voltage (d.c.) (Uc)
Max. continuous operating voltage (a.c.) (Uc)
Max. input voltage acc. to EN 60079-11 (Ui)
Max. input current acc. to EN 60079-11 (Ii)
D1 Total lightning impulse current (10/350 µs) (Iimp)
D1 Lightning impulse current (10/350 µs) per line (Iimp)
C2 Total nominal discharge current (8/20 µs) (In)
C2 Nominal discharge current (8/20 µs) per line (In)
Voltage protection level line-line for Iimp D1 (Up)
Voltage protection level line-PG for Iimp D1 (Up)
Voltage protection level line-line for In C2 (Up)
Voltage protection level line-PG for In C2 (Up)
Voltage protection level line-line at 1 kV/µs C3 (Up)
Voltage protection level line-PG at 1 kV/µs C3 (Up)
Series resistance per line
Cut-off frequency line-line (fG)
Capacitance line-line (C)
Capacitance line-PG (C)
Operating temperature range (TU)
Degree of protection (with plugged-in protection module)
Plugs into
Earthing via
Enclosure material
Colour
Test standards
Approvals *)
SIL classification
ATEX approvals (1)
ATEX approvals (2)
IECEx approvals (1)
IECEx approvals (2)
CSA & USA Hazloc approvals (1)
CSA & USA Hazloc approvals (2)
Inmetro approvals
Weight
GTIN
PU
Part No.
*) For more detailed information, please visit www.dehn-international.com.
  • BXT ML4 BC EX 24
  • 920 384
  • T
  • LifeCheck
  • 24 V
  • 33 V
  • 23.3 V
  • 30 V
  • 0.5 A
  • 4 kA
  • 1 kA
  • 20 kA
  • 5 kA
  • ≤ 53 V
  • ≤ 1300 V
  • ≤ 55 V
  • ≤ 1400 V
  • ≤ 45 V
  • ≤ 1100 V
  • 1 ohm
  • 6.4 MHz
  • ≤ 0.8 nF
  • ≤ 16 pF
  • -40 °C ... +80 °C
  • IP 20
  • base part
  • base part
  • polyamide PA 6.6
  • blue
  • IEC 61643-21 / EN 61643-21, UL 497B
  • CSA, EACEx, ATEX, IECEx, CSA & USA Hazloc, SIL, Inmetro
  • up to SIL3 *)
  • KEMA 06ATEX0274 X: II 2 (1) G Ex ia [ia Ga] IIC T4 ... T6 Gb
  • KEMA 06ATEX0274 X: II 2 G Ex ib IIC T4 ... T6 Gb
  • DEK 11.0078X: Ex ia [ia Ga] IIC T4 ... T6 Gb
  • DEK 11.0078X: Ex ib IIC T4 ... T6 Gb
  • 70000011: Class I Div. 1; Class I Zone 1
  • 70000011: Ex ia [ia] IIC T4 ... T6
  • TÜV 17.0697 X: Ex ia [ia Ga] IIC T6 ... T4 Gb
  • 22 g
  • 4013364109162
  • 1 pc(s)
  • 920 384
  • Specifications (PDF)
  • More

BXT ML2 BD HF EX 6

Basic circuit diagram BXT ML2 BD HF EXDimension drawing BXT ML2 BD HF EX

Space-saving LifeCheck-equipped surge arrester module for protecting one pair in intrinsically safe measuring circuits and RS485 bus systems. Insulation strength > 500 V line-earth.
If LifeCheck detects thermal and electrical overload, the arrester has to be replaced. This status is indicated contactlessly by DEHNrecord LC / SCM / MCM.


Specifications

Type
Part No.
SPD class
SPD monitoring
Nominal voltage (UN)
Max. continuous operating voltage (d.c.) (Uc)
Max. continuous operating voltage (a.c.) (Uc)
Max. input voltage acc. to EN 60079-11 (Ui)
Max. input current acc. to EN 60079-11 (Ii)
Max. input current acc. to EN 60079-11 (without protection module only up to 60 °C) (Ii)
D1 Lightning impulse current (10/350 µs) per line (Iimp)
C2 Total nominal discharge current (8/20 µs) (In)
C2 Nominal discharge current (8/20 µs) line-line (In)
C2 Nominal discharge current (8/20 µs) per line (In)
Voltage protection level line-line for In C2 (Up)
Voltage protection level line-PG for In C2 (Up)
Voltage protection level line-line at 1 kV/µs C3 (Up)
Voltage protection level line-PG at 1 kV/µs C3 (Up)
Cut-off frequency line-line (fG)
Capacitance line-line (C)
Capacitance line-PG (C)
Operating temperature range (TU)
Degree of protection (with plugged-in protection module)
Plugs into
Earthing via
Enclosure material
Colour
Test standards
Approvals *)
SIL classification
ATEX approvals (1)
ATEX approvals (2)
IECEx approvals (1)
IECEx approvals (2)
CSA & USA Hazloc approvals (1)
CSA & USA Hazloc approvals (2)
Inmetro approvals
Weight
GTIN
PU
Part No.
*) For more detailed information, please visit www.dehn-international.com.
  • BXT ML2 BD HF EX 6
  • 920 538
  • T
  • LifeCheck
  • 6 V
  • 6 V
  • 4.2 V
  • 4.2 V
  • 4.8 A
  • 4.8 A
  • 1 kA
  • 10 kA
  • 300 A
  • 5 kA
  • ≤ 35 V
  • ≤ 1800 V
  • ≤ 20 V
  • ≤ 1400 V
  • 100 MHz
  • ≤ 25 nF
  • ≤ 20 pF
  • -40 °C ... +80 °C
  • IP 20
  • base part
  • base part
  • polyamide PA 6.6
  • blue
  • IEC 61643-21 / EN 61643-21
  • EACEx, ATEX, IECEx, CSA & USA Hazloc, SIL, Inmetro
  • up to SIL3 *)
  • KEMA 06ATEX0274 X: II 2 (1) G Ex ia [ia Ga] IIC T4 ... T6 Gb
  • KEMA 06ATEX0274 X: II 2 G Ex ib IIC T4 ... T6 Gb
  • DEK 11.0078X: Ex ia [ia Ga] IIC T4 ... T6 Gb
  • DEK 11.0078X: Ex ib IIC T4 ... T6 Gb
  • 70000011: Class I Div. 1; Class I Zone 1
  • 70000011: Ex ia [ia] IIC T4 ... T6
  • TÜV 17.0697 X: Ex ib IIC T6 ... T4 Gb
  • 20 g
  • 4013364125285
  • 1 pc(s)
  • 920 538
  • Specifications (PDF)
  • More

BXT M2 BD S EX 24

Basic circuit diagram BXT M2 BD S EX 24Dimension drawing BXT M2 BD S EX 24

Space-saving surge arrester module for protecting one pair of intrinsically safe measuring circuits and bus systems, direct or indirect shield earthing, insulation strength > 500 V line-earth.


Specifications

Type
Part No.
SPD class
Nominal voltage (UN)
Max. continuous operating voltage (d.c.) (Uc)
Max. continuous operating voltage (a.c.) (Uc)
Max. input voltage acc. to EN 60079-11 (Ui)
Max. input current acc. to EN 60079-11 (Ii)
D1 Total lightning impulse current (10/350 µs) (Iimp)
D1 Lightning impulse current (10/350 µs) per line (Iimp)
C2 Total nominal discharge current (8/20 µs) (In)
C2 Nominal discharge current (8/20 µs) per line (In)
Voltage protection level line-line for Iimp D1 (Up)
Voltage protection level line-PG for Iimp D1 (Up)
Voltage protection level line-line for In C2 (Up)
Voltage protection level line-PG for In C2 (Up)
Voltage protection level line-line at 1 kV/µs C3 (Up)
Voltage protection level line-PG at 1 kV/µs C3 (Up)
Series resistance per line
Cut-off frequency line-line (fG)
Capacitance line-line (C)
Capacitance line-PG (C)
Operating temperature range (TU)
Degree of protection (with plugged-in protection module)
Plugs into
Earthing via
Enclosure material
Colour
Test standards
Approvals *)
ATEX approvals (1)
ATEX approvals (2)
IECEx approvals (1)
IECEx approvals (2)
CSA & USA Hazloc approvals (1)
CSA & USA Hazloc approvals (2)
Weight
GTIN
PU
Part No.
*) For details see: www.dehn-international.com
  • BXT M2 BD S EX 24
  • 920 383
  • T
  • 24 V
  • 36 V
  • 25.4 V
  • 30 V
  • 0.5 A
  • 4 kA
  • 1 kA
  • 10 kA
  • 5 kA
  • ≤ 55 V
  • ≤ 1300 V
  • ≤ 58 V
  • ≤ 1400 V
  • ≤ 50 V
  • ≤ 1100 V
  • 1.0 ohm
  • 7.7 MHz
  • ≤ 0.8 nF
  • ≤ 16 pF
  • -40 °C ... +80 °C
  • IP 20
  • base part
  • base part
  • polyamide PA 6.6
  • blue
  • IEC 61643-21 / EN 61643-21
  • ATEX, IECEx, CSA & USA Hazloc, SIL
  • KEMA 09ATEX0178 X: II 2 (1) G Ex ia IIC T4 ... T6 Gb
  • KEMA 09ATEX0177 X: II 3 G Ex nA II T4 ... T6 Gc
  • KEM 09.0077X: Ex ia [ia Ga] IIC T4 ... T6 Gb
  • KEM 09.0077X: Ex nA IIC T4 ... T6 Gc
  • 2392869: Class I Div. 1; Class I Zone 1
  • 2392869: Ex ia IIC T4 ... T6
  • 21 g
  • 4013364126725
  • 1 pc(s)
  • 920 383
  • Specifications (PDF)
  • More

Accessories

BXT BAS EX

Base part for use as feed-through terminal in intrinsically safe circuits for the insertion of a protection module without signal disconnection if the protection module is removed.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Colour
Weight
GTIN
PU

Earthing Module

For directly earthing cores connected to the BLITZDUCTOR XT / XTU / SP base part.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Colour
Weight
GTIN
PU

Test / Disconnection Module

Module for testing lines, plugs into BLITZDUCTOR XT / XTU / SP base parts.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Colour
Weight
GTIN
PU

EMC Spring Terminals

Two spring terminals for permanent low-impedance shield contact with the protected and unprotected side of a BLITZDUCTOR XT / XTU / SP arrester. With integrated coding for direct or indirect shield earthing. Cable ties and insulating strips are included. Suitable for BXT(U) ML2 ...S ... / BSP M2 ... types (only direct shield earthing).

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Accessories
Clamping range (mm)
Weight
GTIN
PU
  • SAK BXT LR
  • 920 395
  • cable tie, insulating strips
  • 3-10
  • 12 g/Sa
  • 4013364118157
  • 1 Sa
  • Specifications (PDF)
  • More
    • Further Pictures
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      EMC spring terminals of type SAK BXT LR
      2 spring terminals for permanent low-impedant 
      shield contact to the protected and unprotected side 
      of a BLITZDUCTOR XT.
      With integrated terminal coding for direct or indirect 
      shield earthing, with cable ties and insulating cap.

      delivery and installation.

      Brand: DEHN
      Type: SAK BXT LR
      Part No.: 920 395

      or equivalent.
      Installation Instructions
      Certificates
      CE_SAK_BXT_LR

Partition

Allows to position BXT devices for non-intrinsically safe circuits directly next to intrinsically safe circuits (thread measure ≥ 50 mm).
For DRC MCM XT and DRC SCM XT; 1 set = 2 pieces.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Colour
Weight
GTIN
PU
  • TW DRC MCM EX
  • 910 697
  • blue
  • 31 g/Sa
  • 4013364123717
  • 1 Sa
  • Specifications (PDF)
  • More
    • Further Pictures
      Further Information
      Product Specifications (Text)

      Back

      TW DRC MCM EX partition
      Ex(i) partition
      for maintaining a minimum distance (thread measure) 
      of at least 50 mm between intrinsically safe and 
      non-intrinsically safe circuits according to EN 60079-11
      For 7 mm and 35 mm DIN rails
      Polyamide PA 6.6, blue

      delivery and installation.

      Brand: DEHN
      Type: TW DRC MCM EX
      Part No.: 910 697

      or equivalent.
      Installation Instructions

DRC MCM XT

DIN rail mounted device with integrated LifeCheck sensor for condition monitoring of max. 10 LifeCheck-equipped BXT / BXTU arresters. An RS 485 interface allows to interconnect up to 15 DRC MCM XT.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Colour
Weight
GTIN
PU
  • DRC MCM XT
  • 910 695
  • grey
  • 180 g
  • 4013364118959
  • 1 pc(s)
  • Specifications (PDF)
  • More
    • Further Pictures
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DRC MCM XT DIN rail mounted device with LifeCheck sensor 
      DIN rail mounted device with integrated LifeCheck 
      sensor for condition-based monitoring of max. 10 
      BXT devices with LifeCheck. Visual operating 
      state indication combined with remote signalling 
      contact, break or make contact can be selected. 
      BXT devices to be monitored can be pre-programmed by 
      means of DRC MCM via a PC and a standard RS 485 
      adapter or by means of DRC LC M3.

      delivery and installation.

      Brand: DEHN
      Type: DRC MCM XT
      Part No.: 910 695

      or equivalent.
      Installation Instructions
      Certificates
      CE_DRC_MCM_XT

DRC SCM XT

DIN rail mounted device with integrated LifeCheck sensor for condition monitoring of max. 10 LifeCheck-equipped BXT / BXTU arresters.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Colour
Weight
GTIN
PU

DRC LC M3+

Portable device with LifeCheck sensor for flexible use. Fast and easy testing of LifeCheck-equipped arresters. Documentation via PC database.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Dimensions of storage case
Weight
GTIN
PU
  • DRC LC M3+
  • 910 653
  • 340 x 275 x 83  mm
  • 1,06 kg
  • 4013364113008
  • 1 pc(s)
  • Specifications (PDF)
  • More
    • Further Pictures
      Further Information
      Product Specifications (Text)

      Back

      Portable DRC LC M3+ device with LifeCheck sensor 
      Portable SPD tester for BLITZDUCTOR 
      surge arrester modules with LifeCheck, 
      RFID reader with snap-on LifeCheck sensor 
      Testing within a matter of seconds thanks to visual and 
      acoustic signal and additional USB connection for PC-
      aided management of the specimens and 
      documentation of the test results
      The storage case contains a
      reader, LifeCheck sensor, USB cable, 
      software, loading device and a reference test 
      module.

      delivery and installation.

      Brand: DEHN
      Type: DRC LC M3+
      Part No.: 910 653

      or equivalent.
      Installation Instructions
      Certificates
      CE_DRC_LC_M3+

DRC LC M1+

Portable device with LifeCheck sensor for flexible use. Fast and easy testing of LifeCheck-equipped arresters.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Dimensions of storage case
Weight
GTIN
PU
  • DRC LC M1+
  • 910 655
  • 275 x 230 x 83 mm
  • 835 g
  • 4013364149250
  • 1 pc(s)
  • Specifications (PDF)
  • More
    • Further Pictures
      Further Information
      Product Specifications (Text)

      Back

      Portable DRC LC M1+ device with LifeCheck sensor 
      Portable SPD tester for
      BLITZDUCTOR surge arrester modules
      with LifeCheck, designed as RFID
      reader with snap-on LifeCheck sensor.
      Testing within a matter of seconds
      via visual indication.
      The storage case includes
      a reader, LifeCheck sensor,
      USB cable, charger with country-specific
      adapters and a reference test module.

      delivery and installation.

      Brand: DEHN
      Type: DRC LC M1+
      Part No.: 910 655

      or equivalent.
      Installation Instructions
      Certificates
      CE_DRC_LC_M1+

LifeCheck Sensor for DRC BXT

Snap-on LifeCheck sensor and test module for use as spare part / extension for portable LifeCheck test devices.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
For testing
Weight
GTIN
PU

DEHNpanel

Visual remote indicator for (multiple) surge protective devices (SPDs)

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Operating state/fault indication
Enclosure material
Weight
GTIN
PU
  • DPAN L
  • 910 200
  • green LED (flashing) / red LED (flashing)
  • noryl
  • 140 g
  • 4013364144019
  • 1 pc(s)
  • Specifications (PDF)
  • More
    • Further Pictures
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DPAN L visual remote indication for surge protective devices
      Visual remote indicator with current-saving LEDs for surge protective devices (SPDs) 
      With remote signalling contact
      Also suited for alarm signalling of other devices with floating changeover contact
      For installation in switchgear cabinet doors.
      Power supply: 2x 1.5 V AA batteries
      Degree of protection: IP 40
      Mounting dimensions: 92 x 45 mm
      Dimensions: 96 x 48 x 75 mm

      delivery and installation.

      Brand: DEHN
      Type: DPAN L
      Part No.: 910 200

      or equivalent.
      Installation Instructions
      Certificates
      CE_DEHNpanel