DEHNcord

Flexible surge protection

For protecting electronic devices (e.g. LED lights) from surges. For flexible installation in electrical installation systems such as flush-type boxes, flush-mounted systems, cable ducts and wall boxes. For installation in conformity with the lightning protection zone concept at the boundaries from 0B– 1 and higher.
  • Single-pole, two-pole or three-pole surge protective device with monitoring system and disconnector
  • Visual fault indication
  • Types with disconnection of the load circuit in the event of a fault and protection of the control phase
  • Compact design also for outdoor use
  • Can be fitted in junction boxes, flush-mounted systems, cable ducts and flush-type boxes

Design

DEHNcord L 1P …: Compact single-pole version; for use in flush-type boxes, flush-mounted systems and cable ducts
DEHNcord L 2P …: Compact two-pole version; for use in flush-type boxes, flush-mounted systems and cable ducts
DEHNcord L 3P … SO LTG: Compact three-pole version; for use in the junction boxes of LED light poles with disconnection of the load circuit in the event of a fault and protection of the control phase
DEHNcord R 3P …: Compact three-pole version; for use with electric shutters and blinds

Details

The DEHNcord series can be flexibly used as type 2 surge arrester, thus offering a variety of different application options. Compact in design, the surge arresters are ideally suited for protecting electrical and electronic loads in final circuits wherever the performance of a standard type 3 surge protective device for terminal equipment reaches its limits. An important field of application is the protection of outdoor LED lights. This can be achieved by the DEHNcord L … SO LTG type which can be integrated in the junction box of an LED light pole. This device additionally allows a control phase to be protected and the load circuit to be interrupted if the DEHNcord arrester is faulty. This makes it considerably easier to detect faults, thus facilitating testing and maintenance of the system. DEHNcord is classed a type 2 surge arrester and can therefore be installed according to the lightning protection zones concept at the transition from 0B – 1 and higher. This ensures proper installation of surge protective devices wherever space is restricted. Despite the powerful protective circuit, the compact enclosure of the DEHNcord devices also houses a disconnector and a visual operating state / fault indicator. Be it in junction boxes, cable ducts, flush-mounted systems, junction boxes or device casings: There is always enough space for DEHNcord in the relevant installation environment.

Cost-effective, compact type for two LED. One DCOR for an optimal surge protection of two LED lamps.

Thanks to its adapted design, the LTG type is ideally suited for integration in the upper area of the EK480 junction box (fuse box) from Langmatz.
The IP type can both be integrated in junction boxes and directly in the mast (cables can be entered into any junction box (fuse box) thanks to IP 65 degree of protection).

The multipole DEHNcord R 3P adapter is a type 2 surge arrester with monitoring device and disconnector for installation in the connection cable of the motor of electric blinds or shutters to protect them and building installation against surge induced on the building facade.
By installing this device you meet the requirements of the lightning protection zone conept as well as installation standard for buildings IEC 60364-4-44/-5-53 (DIN VDE 0100-443/-534.S).

Models

DEHNcord L 2P

DEHNcord L 1P

DEHNcord L 3P 275 SO LTG

DEHNcord L 2P 275 SO LTG

DEHNcord L 2P SN1860

DEHNcord L 2P 275 SO LT

DEHNcord L 2P SN1864

DEHNcord L 3P 275 SO IP

DEHNcord L 2P 275 SO IP

+
DEHNcord R 3P

DEHNcord L 2P

Basic circuit diagram DCOR L 2P ...Dimension drawing DCOR L 2P ...

Two-pole surge arrester for all installation systems (1+1 configuration); compact design.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) [L-N] (UC)
Max. continuous operating voltage (a.c.) [N-PE] (UC)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Total discharge current (8/20 µs) [L+N-PE] (Itotal)
Voltage protection level [L-N] (UP)
Voltage protection level [L-N] at 3 kA (UP)
Voltage protection level [L-N] at 1.5 kA (UP)
Voltage protection level [N-PE] (UP)
Follow current extinguishing capability [N-PE] (Ifi)
Response time [L-N] (tA)
Response time [L/N-PE] (tA)
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection (ISCCR)
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic
Operating state / fault indication
Number of ports
Operating temperature range (TU)
Connecting wires
Enclosure material
Place of installation
Degree of protection of installed device
Approvals
Weight
GTIN
PU
Part No.
  • DCOR L 2P 275
  • 900 430
  • type 2 / class II
  • type 2 + type 3
  • 230 V (50 / 60 Hz)
  • 275 V (50 / 60 Hz)
  • 255 V (50 / 60 Hz)
  • 5 kA
  • 10 kA
  • 20 kA
  • ≤ 1.5 kV
  • ≤ 1 kV
  • ≤ 0.85 kV
  • ≤ 1.5 kV
  • 100 Arms
  • ≤ 25 ns
  • ≤ 100 ns
  • 25 A gG
  • 25 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • 1200 V / 200 ms – withstand
  • green / red
  • 1
  • -40 °C ... +80 °C
  • 1.5 mm2, 200 mm long
  • thermoplastic, red, UL 94 V-2
  • indoor installation
  • IP 20
  • KEMA
  • 59 g
  • 4013364157286
  • 1 pc(s)
  • 900 430
  • Specifications (PDF)
  • More
  • DCOR L 2P 320
  • 900 432
  • type 2 / class II
  • type 2 + type 3
  • 230 / 277 V (50 / 60 Hz)
  • 320 V (50 / 60 Hz)
  • 255 V (50 / 60 Hz)
  • 5 kA
  • 10 kA
  • 20 kA
  • ≤ 1.75 kV
  •  
  •  
  • ≤ 1.5 kV
  • 100 Arms
  • ≤ 25 ns
  • ≤ 100 ns
  • 25 A gG
  • 25 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • 1200 V / 200 ms – withstand
  • green / red
  • 1
  • -40 °C ... +80 °C
  • 1.5 mm2, 200 mm long
  • thermoplastic, red, UL 94 V-2
  • indoor installation
  • IP 20
  • KEMA
  • 61 g
  • 4013364157309
  • 1 pc(s)
  • 900 432
  • Specifications (PDF)
  • More

DEHNcord L 1P

Basic circuit diagram DCOR L 1P ...Dimension drawing DCOR L 1P ...

Single-pole surge arrester for all installation systems; compact design.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) [L-N] (UC)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Voltage protection level [L-N] (UP)
Voltage protection level [L-N] at 3 kA (UP)
Voltage protection level [L-N] at 1.5 kA (UP)
Response time [L-N] (tA)
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection (ISCCR)
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Operating state / fault indication
Number of ports
Operating temperature range (TU)
Connecting wires
Enclosure material
Place of installation
Degree of protection of installed device
Approvals
Weight
GTIN
PU
Part No.
  • DCOR L 1P 275
  • 900 431
  • type 2 / class II
  • type 2 + type 3
  • 230 V (50 / 60 Hz)
  • 275 V (50 / 60 Hz)
  • 5 kA
  • 10 kA
  • ≤ 1.5 kV
  • ≤ 1 kV
  • ≤ 0.85 kV
  • ≤ 25 ns
  • 25 A gG
  • 25 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • green / red
  • 1
  • -40 °C ... +80 °C
  • 1.5 mm2, 200 mm long
  • thermoplastic, red, UL 94 V-2
  • indoor installation
  • IP 20
  • KEMA
  • 46 g
  • 4013364310827
  • 1 pc(s)
  • 900 431
  • Specifications (PDF)
  • More
  • DCOR L 1P 320
  • 900 433
  • type 2 / class II
  • type 2 + type 3
  • 230 / 277 V (50 / 60 Hz)
  • 320 V (50 / 60 Hz)
  • 5 kA
  • 10 kA
  • ≤ 1.75 kV
  •  
  •  
  • ≤ 25 ns
  • 25 A gG
  • 25 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • green / red
  • 1
  • -40 °C ... +80 °C
  • 1.5 mm2, 200 mm long
  • thermoplastic, red, UL 94 V-2
  • indoor installation
  • IP 20
  • KEMA
  • 48 g
  • 4013364157316
  • 1 pc(s)
  • 900 433
  • Specifications (PDF)
  • More

DEHNcord L 3P 275 SO LTG

Basic circuit diagram DCOR L 3P 275 SO LTGDimension drawing DCOR L 3P 275 SO LTG

Three-pole surge arrester for all installation systems; compact design.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) [L-N] (UC)
Max. continuous operating voltage (a.c.) [N-PE] (UC)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Total discharge current (8/20 µs) [L+N-PE] (Itotal)
Voltage protection level [L-N] (UP)
Voltage protection level [L-N] at 3 kA (UP)
Voltage protection level [L-N] at 1.5 kA (UP)
Voltage protection level [N-PE] (UP)
Follow current extinguishing capability [N-PE] (Ifi)
Response time [L-N] (tA)
Response time [L/N-PE] (tA)
Max. load current (IL)
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection (ISCCR)
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gG (ISCCR)
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic
Fault indication
Interruption of the load circuit in the event of a fault
Number of ports
Operating temperature range (TU)
Connecting wires
Enclosure material
Place of installation
Degree of protection of installed device
Approvals
Extended technical data:
Combination wave (UOC)
Weight
GTIN
PU
Part No.
  • DCOR L 3P 275 SO LTG
  • 900 445
  • type 2 / class II
  • type 2 + type 3
  • 230 V (50 / 60 Hz)
  • 275 V (50 / 60 Hz)
  • 255 V (50 / 60 Hz)
  • 5 kA
  • 10 kA
  • 20 kA
  • ≤ 1.5 kV
  • ≤ 1 kV
  • ≤ 0.85 kV
  • ≤ 1.5 kV
  • 100 Arms
  • ≤ 25 ns
  • ≤ 100 ns
  • 10 A
  • B 16 A
  • 1 kArms
  • 6 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • 1200 V / 200 ms – safe failure
  • red
  • yes
  • 1
  • -40 °C ... +80 °C
  • 1.5 mm2, 60 mm long
  • thermoplastic, red, UL 94 V-2
  • indoor installation, fuse box for mast installation
  • IP 20
  • KEMA
  • ------------------------------------
  • 10 kV
  • 58 g
  • 4013364280380
  • 1 pc(s)
  • 900 445
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram DCOR L 3P 275 SO LTG
      open PDF
      Dimension drawing DCOR L 3P 275 SO LTG
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DEHNcord L 3P 275 SO LTG surge arrester
      Multipole type 2 surge arrester according to EN 61643-11
      for installation in junction boxes. 
      Protection of the control phase 
      LED can be disconnected in case of a fault
      Integrated separate visual fault indication for the supply voltage and control phase
      Max. continuous operating voltage: 275 V a.c.
      Voltage protection level: <= 1.5 kV
      Nominal discharge current (8/20): 5 kA
      Total discharge current (8/20):	20 kA
      Follow current extinguishing capability [N-PE]:             100 A rms
      Max. mains-side overcurrent protection: 16 A gG
      Max. load current (a.c.): 10 A
      Energy coordination with arresters
      of the Red/Line series according to EN 62305-4

      delivery and installation.

      Brand: DEHN
      Type: DCOR L 3P 275 SO LTG
      Part No.: 900 445

      or equivalent.
      Installation Instructions
      Certificates
      2187911.01
      CE_DCOR_L_3P_275_SO_LTG
      CAD-Data for registered Users
      900445.stp
      900445.igs
      900445.jt
      900445.dwg
      900445m_D.dxf

DEHNcord L 2P 275 SO LTG

Basic circuit diagram DCOR L 2P 275 SO LTGDimension drawing DCOR L 2P 275 SO LTG

Two-pole surge arrester for all installation systems; compact design.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) [L-N] (UC)
Max. continuous operating voltage (a.c.) [N-PE] (UC)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Voltage protection level [L-N] (UP)
Voltage protection level [L-N] at 3 kA (UP)
Voltage protection level [L-N] at 1.5 kA (UP)
Voltage protection level [N-PE] (UP)
Follow current extinguishing capability [N-PE] (Ifi)
Response time [L-N] (tA)
Response time [L/N-PE] (tA)
Max. load current (IL)
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection (ISCCR)
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gG (ISCCR)
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic
Fault indication
Interruption of the load circuit in the event of a fault
Number of ports
Operating temperature range (TU)
Connecting wires
Enclosure material
Place of installation
Degree of protection of installed device
Approvals
Additional tests:
– Total discharge current (Isum)
Extended technical data:
Combination wave (UOC)
Weight
GTIN
PU
Part No.
  • DCOR L 2P 275 SO LTG
  • 900 446
  • type 2 / class II
  • type 2 + type 3
  • 230 V (50 / 60 Hz)
  • 275 V (50 / 60 Hz)
  • 255 V (50 / 60 Hz)
  • 5 kA
  • 10 kA
  • ≤ 1.5 kV
  • ≤ 1 kV
  • ≤ 0.85 kV
  • ≤ 1.5 kV
  • 100 Arms
  • ≤ 25 ns
  • ≤ 100 ns
  • 10 A
  • B 16 A
  • 1 kArms
  • 6 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • 1200 V / 200 ms – safe failure
  • red
  • yes
  • 1
  • -40 °C ... +80 °C
  • 1.5 mm2, 60 mm long
  • thermoplastic, red, UL 94 V-2
  • indoor installation, fuse boxes for mast installation
  • IP 20
  • KEMA
  • ------------------------------------
  • 20 kA
  • ------------------------------------
  • 10 kV
  • 49 g
  • 4013364292970
  • 1 pc(s)
  • 900 446
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram DCOR L 2P 275 SO LTG
      open PDF
      Dimension drawing DCOR L 2P 275 SO LTG
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DEHNcord L 2P 275 SO LTG surge arrester
      Multipole type 2 surge arrester according to EN 61643-11
      with cables for installation in junction boxes. 
      LED can be disconnected in case of a fault
      Integrated visual fault indication for the supply voltage 
      Max. continuous operating voltage: 275 V a.c.
      Voltage protection level: <= 1.5 kV
      Nominal discharge current (8/20): 5 kA
      Summary discharge current:	20 kA
      Follow current extinguishing capability [N-PE]:             100 A rms
      Max. mains-side overcurrent protection: 16 A gG
      Max. load current (a.c.): 10 A
      Energy coordination with arresters
      of the Red/Line series according to EN 62305-4

      delivery and installation.

      Brand: DEHN
      Type: DCOR L 2P 275 SO LTG
      Part No.: 900 446

      or equivalent.
      Installation Instructions
      Certificates
      2193652.01
      CE_DCOR_L_2P_275_SO_LTG
      CAD-Data for registered Users
      900446.stp
      900446.igs
      900446.jt
      900446.dwg
      900446m_D.dxf

DEHNcord L 2P SN1860

Basic circuit diagram DCOR L 2P SN1860Dimension drawing DCOR L 2P SN1860

Two-pole surge arrester for all installation systems; compact design.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) [L-N] (UC)
Max. continuous operating voltage (a.c.) [N-PE] (UC)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Voltage protection level [L-N] (UP)
Voltage protection level [L-N] at 3 kA (UP)
Voltage protection level [L-N] at 1.5 kA (UP)
Voltage protection level [N-PE] (UP)
Follow current extinguishing capability [N-PE] (Ifi)
Response time [L-N] (tA)
Response time [L/N-PE] (tA)
Max. load current (IL)
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection (ISCCR)
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gG (ISCCR)
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic
Fault indication
Interruption of the load circuit in the event of a fault
Number of ports
Operating temperature range (TU)
Connecting wires
Enclosure material
Place of installation
Degree of protection of installed device
Additional tests:
– Total discharge current (Isum)
Extended technical data:
Combination wave (UOC)
Weight
GTIN
PU
Part No.
  • DCOR L 2P SN1860
  • 999 937
  • type 2 / class II
  • type 2 + type 3
  • 230 V (50 / 60 Hz)
  • 275 V (50 / 60 Hz)
  • 255 V (50 / 60 Hz)
  • 5 kA
  • 10 kA
  • ≤ 1.5 kV
  • ≤ 1 kV
  • ≤ 0.85 kV
  • ≤ 1.5 kV
  • 100 Arms
  • ≤ 25 ns
  • ≤ 100 ns
  • 10 A
  • B 16 A
  • 1 kArms
  • 6 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • 1200 V / 200 ms – safe failure
  • red
  • yes
  • 1
  • -40 °C ... +80 °C
  • 1.5 mm2, 160 mm long
  • thermoplastic, red, UL 94 V-2
  • indoor installation, fuse boxes for mast installation
  • IP 20
  • ------------------------------------
  • 20 kA
  • ------------------------------------
  • 10 kV
  • 56 g
  • 4013364303195
  • 1 pc(s)
  • 999 937
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram DCOR L 2P SN1860
      open PDF
      Dimension drawing DCOR L 2P SN1860
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DEHNcord L 2P SN1860 surge arrester
      Multipole type 2 surge arrester according to EN 61643-11
      with cables for installation in junction boxes. 
      LED can be disconnected in case of a fault
      Integrated visual fault indication for the supply voltage 
      Max. continuous operating voltage: 275 V a.c.
      Voltage protection level: <= 1.5 kV
      Nominal discharge current (8/20): 5 kA
      Summary discharge current:	20 kA
      Follow current extinguishing capability [N-PE]:             100 A rms
      Max. mains-side overcurrent protection: 16 A gG
      Max. load current (a.c.): 10 A
      Energy coordination with arresters
      of the Red/Line series according to EN 62305-4

      delivery and installation.

      Brand: DEHN
      Type: DCOR L 2P SN1860
      Part No.: 999 937

      or equivalent.
      Installation Instructions
      Certificates
      CE_DCOR_L_2P_SN1860
      CAD-Data for registered Users
      999937.stp
      999937.igs
      999937.jt
      999937.dwg
      999937m_D.dxf

DEHNcord L 2P 275 SO LT

Basic circuit diagram DCOR L 2P 275 SO LTDimension drawing DCOR L 2P 275 SO LT

Two-pole surge arrester for all installation systems; compact design.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) [L-PEN] (UC)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Voltage protection level [L-PEN] (UP)
Voltage protection level [L-PEN] at 3 kA (UP)
Voltage protection level [L-PEN] at 1.5 kA (UP)
Response time [L-PEN] (tA)
Max. load current (IL)
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection (ISCCR)
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gG (ISCCR)
Temporary overvoltage (TOV) [L-PEN] (UT) – Characteristic
Temporary overvoltage (TOV) [L-PEN] (UT) – Characteristic
Fault indication
Interruption of the load circuit in the event of a fault
Number of ports
Operating temperature range (TU)
Connecting wires
Enclosure material
Place of installation
Degree of protection of installed device
Approvals
Additional tests:
– Total discharge current (Isum)
Extended technical data:
Combination wave (UOC)
Weight
GTIN
PU
Part No.
  • DCOR L 2P 275 SO LT
  • 900 435
  • type 2 / class II
  • type 2 + type 3
  • 230 V (50 / 60 Hz)
  • 275 V (50 / 60 Hz)
  • 5 kA
  • 10 kA
  • ≤ 1.5 kV
  • ≤ 1 kV
  • ≤ 0.85 kV
  • ≤ 25 ns
  • 10 A
  • B 16 A
  • 1 kArms
  • 6 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • red
  • yes
  • 1
  • -40 °C ... +80 °C
  • 1.5 mm2, 60 mm long
  • thermoplastic, red, UL 94 V-2
  • indoor installation, fuse box for mast installation
  • IP 20
  • KEMA
  • ------------------------------------
  • 20 kA
  • ------------------------------------
  • 10 kV
  • 54 g
  • 4013364292963
  • 1 pc(s)
  • 900 435
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram DCOR L 2P 275 SO LT
      open PDF
      Dimension drawing DCOR L 2P 275 SO LT
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DEHNcord L 2P 275 SO LT surge arrester
      Multipole type 2 surge arrester according to EN 61643-11
      with cables for installation in junction boxes. 
      Protection of the control phase 
      LED can be disconnected in case of a fault
      Integrated visual fault indication for the supply voltage 
      Max. continuous operating voltage: 275 V a.c.
      Voltage protection level: <= 1.5 kV
      Nominal discharge current (8/20): 5 kA
      Summary discharge current:	20 kA
      Max. mains-side overcurrent protection: 16 A gG
      Max. load current (a.c.): 10 A
      Energy coordination with arresters
      of the Red/Line series according to EN 62305-4

      delivery and installation.

      Brand: DEHN
      Type: DCOR L 2P 275 SO LT
      Part No.: 900 435

      or equivalent.
      Installation Instructions
      Certificates
      CE_DCOR_L_2P_275_SO_LT
      2193652.01
      CAD-Data for registered Users
      900435.stp
      900435.igs
      900435.jt
      900435.dwg
      900435m_D.dxf

DEHNcord L 2P SN1864

Basic circuit diagram DCOR L 2P SN1864Dimension drawing DCOR L 2P SN1864

Surge arrester for all installation systems; compact design.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) [L-N] (UC)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Voltage protection level [L-N] (UP)
Voltage protection level [L-N] at 3 kA (UP)
Voltage protection level [L-N] at 1.5 kA (UP)
Response time [L-N] (tA)
Max. load current (IL)
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection (ISCCR)
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gG (ISCCR)
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Fault indication
Interruption of the load circuit in the event of a fault
Number of ports
Operating temperature range (TU)
Connecting wires
Enclosure material
Place of installation
Degree of protection of installed device
Additional tests:
– Total discharge current (Isum)
Weight
GTIN
PU
Part No.
  • DCOR L 2P SN1864
  • 999 906 +
  • type 2 / class II
  • type 2 + type 3
  • 230 V (50 / 60 Hz)
  • 275 V (50 / 60 Hz)
  • 5 kA
  • 10 kA
  • ≤ 1.5 kV
  • ≤ 1 kV
  • ≤ 0.85 kV
  • ≤ 25 ns
  • 10 A
  • B 16 A
  • 1 kArms
  • 6 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • red
  • yes
  • 1
  • -40 °C ... +80 °C
  • 1.5 mm2, 60 mm long
  • thermoplastic, red, UL 94 V-2
  • indoor installation, fuse box for mast installation
  • IP 20
  • ------------------------------------
  • 20 kA
  • 54 g
  • 4013364310926
  • 1 pc(s)
  • 999 906
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram DCOR L 2P SN1864
      open PDF
      Dimension drawing DCOR L 2P SN1864
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      Surge arrester DEHNcord L 2P SN1864
      Multi-pole surge arrester Type 2 according to EN 61643-11 
      for use in cable junction boxes. 
      With protection of the control phase
      Disconnection of the light in case of fault and
      integrated visual fault indication 
      for supply voltage
      Max. continuous operating voltage:     275 V ac
      Voltage protection level:	                       <= 1.5 kV
      Nominal discharge current (8/20):         5 kA
      Total discharge current:   		                20 kA
      Max. mains-side overcurrent
      protection:                                                 16 A gG
      Max. load current AC:                               10 A
      Energy coordination acc. to DIN EN 62305-4 
      with arresters of the Red/Line family

      delivery and installation.

      Brand: DEHN
      Type: DCOR L 2P SN1864
      Part No.: 999 906

      or equivalent.
      Installation Instructions
      Certificates
      CE_DCOR_L_2P_SN1864
      CAD-Data for registered Users
      999906.stp
      999906.igs
      999906.jt
      999906.dwg
      999906m_D.dxf

DEHNcord L 3P 275 SO IP

Basic circuit diagram DCOR L 3P 275 SO IPDimension drawing DCOR L 3P 275 SO IP

Three-pole surge arrester for all installation systems; compact design. IP 65 degree of protection.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) [L-N] (UC)
Max. continuous operating voltage (a.c.) [N-PE] (UC)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Total discharge current (8/20 µs) [L+N-PE] (Itotal)
Voltage protection level [L-N] (UP)
Voltage protection level [L-N] at 3 kA (UP)
Voltage protection level [L-N] at 1.5 kA (UP)
Voltage protection level [N-PE] (UP)
Follow current extinguishing capability [N-PE] (Ifi)
Response time [L-N] (tA)
Response time [L/N-PE] (tA)
Max. load current (IL)
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection (ISCCR)
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gG (ISCCR)
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic
Fault indication
Interruption of the load circuit in the event of a fault
Number of ports
Operating temperature range (TU)
Connecting cable
Enclosure material
Place of installation
Degree of protection of installed device
Extended technical data:
Combination wave (UOC)
Weight
GTIN
PU
Part No.
  • DCOR L 3P 275 SO IP
  • 900 447
  • type 2 / class II
  • type 2 + type 3
  • 230 V (50 / 60 Hz)
  • 275 V (50 / 60 Hz)
  • 255 V (50 / 60 Hz)
  • 5 kA
  • 10 kA
  • 20 kA
  • ≤ 1.5 kV
  • ≤ 1 kV
  • ≤ 0.85 kV
  • ≤ 1.5 kV
  • 100 Arms
  • ≤ 25 ns
  • ≤ 100 ns
  • 10 A
  • B 16 A
  • 1 kArms
  • 6 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • 1200 V / 200 ms – safe failure
  • red
  • yes
  • 1
  • -40 °C ... +80 °C
  • 1.5 mm2, 230 mm long
  • thermoplastic, red, UL 94 V-2
  • indoor installation
  • IP 65
  • ------------------------------------
  • 10 kV
  • 130 g
  • 4013364282216
  • 1 pc(s)
  • 900 447
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram DCOR L 3P 275 SO IP
      open PDF
      Dimension drawing DCOR L 3P 275 SO IP
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DEHNcord L 2P 275 SO IP surge arrester
      Multipole type 2 surge arrester according to EN 61643-11
      with cables for outdoor installation (IP65 degree of protection) e.g. on junction boxes. 
      With protection of the control phase
      LED can be disconnected in case of a fault
      Integrated visual fault indication for the supply voltage and control phase 
      With fixing lug
      Max. continuous operating voltage: 275 V a.c.
      Voltage protection level: <= 1.5 kV
      Nominal discharge current (8/20): 5 kA
      Summary discharge current:	20 kA
      Follow current extinguishing capability [N-PE]:             100 A rms
      Max. mains-side overcurrent protection: 16 A gG
      Max. load current (a.c.): 10 A
      Energy coordination with arresters
      of the Red/Line series according to EN 62305-4

      delivery and installation.

      Brand: DEHN
      Type: DCOR L 3P 275 SO IP
      Part No.: 900 447

      or equivalent.
      Installation Instructions
      Certificates
      CE_DCOR_L_3P_275_SO_IP
      CAD-Data for registered Users
      900447.stp
      900447.igs
      900447.jt
      900447.dwg
      900447m_D.dxf

DEHNcord L 2P 275 SO IP

Basic circuit diagram DCOR L 2P 275 SO IPDimension drawing DCOR L 2P 275 SO IP

Two-pole surge arrester for all installation systems; compact design. IP 65 degree of protection.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) [L-N] (UC)
Max. continuous operating voltage (a.c.) [N-PE] (UC)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Voltage protection level [L-N] (UP)
Voltage protection level [L-N] at 3 kA (UP)
Voltage protection level [L-N] at 1.5 kA (UP)
Voltage protection level [N-PE] (UP)
Follow current extinguishing capability [N-PE] (Ifi)
Response time [L-N] (tA)
Response time [L/N-PE] (tA)
Max. load current (IL)
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection (ISCCR)
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gG (ISCCR)
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic
Fault indication
Interruption of the load circuit in the event of a fault
Number of ports
Operating temperature range (TU)
Connecting cable
Enclosure material
Place of installation
Degree of protection of installed device
Additional tests:
– Total discharge current (Isum)
Extended technical data:
Combination wave (UOC)
Weight
GTIN
PU
Part No.
  • DCOR L 2P 275 SO IP
  • 900 448
  • type 2 / class II
  • type 2 + type 3
  • 230 V (50 / 60 Hz)
  • 275 V (50 / 60 Hz)
  • 255 V (50 / 60 Hz)
  • 5 kA
  • 10 kA
  • ≤ 1.5 kV
  • ≤ 1 kV
  • ≤ 0.85 kV
  • ≤ 1.5 kV
  • 100 Arms
  • ≤ 25 ns
  • ≤ 100 ns
  • 10 A
  • B 16 A
  • 1 kArms
  • 6 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • 1200 V / 200 ms – safe failure
  • red
  • yes
  • 1
  • -40 °C ... +80 °C
  • 1.5 mm2, 230 mm long
  • thermoplastic, red, UL 94 V-2
  • indoor installation
  • IP 65
  • ------------------------------------
  • 20 kA
  • ------------------------------------
  • 10 kV
  • 113 g
  • 4013364293007
  • 1 pc(s)
  • 900 448
  • Specifications (PDF)
  • More
    • Further Pictures
      open PDF
      Dimension drawing DCOR L 2P 275 SO IP
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DEHNcord L 2P 275 SO IP surge arrester
      Multipole type 2 surge arrester according to EN 61643-11
      with cables for outdoor installation (IP65 degree of protection) e.g. on junction boxes. 
      LED can be disconnected in case of a fault
      Integrated visual fault indication for the supply voltage 
      With fixing lug
      Max. continuous operating voltage: 275 V a.c.
      Voltage protection level: <= 1.5 kV
      Nominal discharge current (8/20): 5 kA
      Summary discharge current:	20 kA
      Follow current extinguishing capability [N-PE]:             100 A rms
      Max. mains-side overcurrent protection: 16 A gG
      Max. load current (a.c.): 10 A
      Energy coordination with arresters
      of the Red/Line series according to EN 62305-4

      delivery and installation.

      Brand: DEHN
      Type: DCOR L 2P 275 SO IP
      Part No.: 900 448

      or equivalent.
      Installation Instructions
      Certificates
      CE_DCOR_L_2P_275_SO_IP
      CAD-Data for registered Users
      900448.stp
      900448.igs
      900448.jt
      900448.dwg
      900448p.dxf

+ DEHNcord R 3P

Basic circuit diagram DCOR R 3P 275Dimension drawing DCOR R 3P 275

Surge arrester for electric Venetian blinds; compact dimensions.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Energy coordination with terminal equipment (≤ 10 m)
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) [L-N] (UC)
Max. continuous operating voltage (a.c.) [N-PE] (UC)
Nominal load current (a.c.) (IL)
Nominal discharge current (8/20 µs) (In)
Max. discharge current (8/20 µs) (Imax)
Total discharge current (8/20 µs) [L+N-PE] (Itotal)
Voltage protection level [L-N] (UP)
Follow current extinguishing capability [N-PE] (Ifi)
Response time [L-N] (tA)
Response time [L/N-PE] (tA)
Short-circuit withstand capability for mains-side overcurrent protection (ISCCR)
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic
Acoustic fault indication
Interruption of the load circuit in the event of a fault
Number of ports
Connector
Operating temperature range (TU)
Degree of protection of installed device
Weight
GTIN
PU
Part No.
  • DCOR R 3P 275
  • 900 449 +
  • type 2 / class II
  • type 2 + type 3
  • 230 V (50 / 60 Hz)
  • 275 V (50 / 60 Hz)
  • 255 V (50 / 60 Hz)
  • 10 A
  • 2,5 kA
  • 5 kA
  • 15 kA
  • ≤ 1.5 kV
  • 100 Arms
  • ≤ 25 ns
  • ≤ 100 ns
  • 1 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • 1200 V / 200 ms – safe failure
  • yes
  • yes for downstream operation
  • 1
  • Hirschmann STAK 3 / STAS 3
  • -20 °C ... +70 °C
  • IP 54
  • 129 g
  • 4013364320031
  • 1 pc(s)
  • 900 449
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram DCOR R 3P 275
      open PDF
      Dimension drawing DCOR R 3P 275
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DEHNcord R 3P 275 surge arrester
      Multipole type 2 surge arrester according to EN 61643-11 
      for outdoor installation (degree of protection IP54) for protecting electric sun blinds/blinds or venetian blinds 
      Interruption of the load circuit in the event of a fault 
      For downstream operation
      Acoustic fault indication for both protective paths
      Max. continuous operating voltage:         275 V a.c.
      Voltage protection level:                            <= 1.5 kV
      Nominal discharge current (8/20):            2.5 kA
      Total discharge current (8/20) [L+N-PE]: 15 kA
      Follow current extinguishing capability [N-PE]: 100 A rms
      Nominal load current (a.c.): 10 A
      Energy coordination according to IEC/EN 62305-4 
      with arresters of the Red/Line series

      delivery and installation.

      Brand: DEHN
      Type: DCOR R 3P 275
      Part No.: 900 449

      or equivalent.
      Installation Instructions
      Certificates
      CE_DCOR_R_3P_275
      CAD-Data for registered Users
      900449.stp
      900449.igs
      900449.jt
      900449.dwg
      900449m_D.dxf