DEHNsafe

Surge Arrester for Use in Cable Ducts

For protecting electronic devices against surges. For installation in electrical installation systems, e.g. cable ducts or flush-type boxes. For installation in conformity with the lightning protection zone concept at the boundaries from 1 – 2 and higher.
  • Two-pole surge protective device for 230 V terminal equipment
  • For use in flush-type boxes and cable ducts
  • Enhanced safety due to fault-proof Y protective circuit
  • Multiple visual indicator
  • Programmable acoustic function
  • Terminals for series connection
  • Independent of the socket outlet design

Version

DEHNsafe 230 LA: Surge protective device for use in cable ducts

Details

DEHNsafe surge arresters particularly stand out due to their flexible application options. Thanks to their small mounting depth of only 31 mm, the two-pole surge protective devices for 230 V terminal equipment can be installed both in cable ducts and in flat flush-type boxes. DEHNsafe incorporates a monitoring device and a thermal disconnector. In addition to a visual operating state indicator, the device features a programmable acoustic fault indicator which can be programmed for three different operating states:
– Acoustic fault indication,
– Test function,
– Muting of the acoustic signal.

DEHNsafe surge arresters are covered by a triple TAE cover from any switch range manufacturer, thus ideally adapting to any socket outlet design.
The double terminals for L, N and PE allow for series connection to ensure that the surge protective device is situated in parallel to the circuit to be protected. For this reason, DEHNsafe does not necessarily interrupt the circuit to be protected in case of overload. They feature a green and red LED for visual inspection.

Figure 1

Models

DEHNsafe

DEHNsafe

Basic circuit diagram DSA 230 LADimension drawing DSA 230 LA

Surge protective device for use in cable ducts and flush-type boxes. For single-phase 230 V TT and TN systems.


Specifications

Type
Part No.
SPD according to EN 61643-11 / IEC 61643-11
Nominal voltage (a.c.) (UN)
Max. continuous operating voltage (a.c.) (UC)
Nominal load current (IL)
Nominal discharge current (8/20 µs) (In)
Total discharge current (8/20 µs) [L+N-PE] (Itotal)
Combination wave (UOC)
Combination wave [L+N-PE] (UOC total)
Voltage protection level [L-N] / [L/N-PE] (UP)
Response time [L-N] (tA)
Response time [L/N-PE] (tA)
Max. mains-side overcurrent protection
Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR)
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic
Temporary overvoltage (TOV) [L/N-PE] (UT) – Characteristic
Temporary overvoltage (TOV) [L/N-PE] (UT) – Characteristic
Temporary overvoltage (TOV) [L+N-PE] (UT) – Characteristic
Fault indication
Operating state indication
Number of ports
Switch
Operating temperature range (TU)
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Place of installation
Degree of protection
Cover
Weight
GTIN
PU
Part No.
  • DSA 230 LA
  • 924 370
  • type 3 / class III
  • 230 V (50 / 60 Hz)
  • 255 V (50 / 60 Hz)
  • 16 A
  • 3 kA
  • 5 kA
  • 6 kV
  • 10 kV
  • ≤ 1250 / ≤ 1500 V
  • ≤ 25 ns
  • ≤ 100 ns
  • B 16 A
  • 1 kArms
  • 335 V / 5 sec. – withstand
  • 440 V / 120 min. – safe failure
  • 335 V / 120 min. – withstand
  • 440 V / 5 sec. – withstand
  • 1200 V + UREF / 200 ms – safe failure
  • red light + acoustic signal
  • green light
  • 1
  • function test / acoustic signal off
  • -25 °C ... +40 °C
  • 0.5 mm2 solid / stranded / flexible
  • 2.5 mm2 solid / stranded / flexible
  • retaining rings (Ø60 mm) for installation in switch boxes (40 mm deep)
  • thermoplastic, grey, UL 94 V-2
  • indoor installation
  • IP 20
  • TAE
  • 71 g
  • 4013364081321
  • 1 pc(s)
  • 924 370
  • Specifications (PDF)
  • More
    • Further Pictures
      Basic circuit diagram DSA 230 LA
      open PDF
      Dimension drawing DSA 230 LA
      open PDF
      Further Information
      Product Specifications (Text)

      Back

      DEHNsafe 230 LA surge protective device for cable ducts
      Two-pole surge arrester for 230 V terminal devices
      Type 3 SPD according to EN 61643-11
      For use in flush-type boxes and cable ducts
      Multiple visual status indication
      Programmable acoustic function
      Max. continuous operating voltage: 255 V a.c.
      Voltage protection level: <= 1.5 kV 
      Total discharge current: 		5 kA
      Max. mains-side overcurrent protection:
      16 A gG or B 16 A
      Energy-coordinated according to IEC 62305-4 with arresters 
      of the Red/Line series

      delivery and installation.

      Brand: DEHN
      Type: DSA 230 LA
      Part No.: 924 370

      or equivalent.
      Installation Instructions
      Certificates
      CE_DSA_230_LA
      CAD-Data for registered Users
      924370m_D.dxf

Accessories

Central Covering Plate

Single unit, alpha exclusive.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Colour
Weight
GTIN
PU

Cover Frame

Single unit, alpha exclusive.

Show SpecificationsHide Specifications

Specifications

Type
Part No.
Colour
Weight
GTIN
PU