DEHNcombo

Combined Arrester for use in Photovoltaic Systems

For protecting photovoltaic inverters against surges and even direct lightning strikes. For use in accordance with IEC 60364-7-712 (Installation of photovoltaic power supply systems).
  • Prewired type 1 and type 2 combined lightning current and surge arrester for use in photovoltaic generator circuits
  • Combined disconnection and short-circuiting device with safe electrical isolation (patented SCI principle)
  • Approved fault-resistant Y circuit prevents damage to the surge protective device in case of insulation faults in the generator circuit
  • Space-saving enclosure with a width of only four modules for up to 1500 V d.c.
  • Tested to EN 50539-11
  • Suitable for use in all PV systems in accordance with IEC 60364-7-712
  • Operating state / fault indication by green / red indicator flag in the inspection window

Type

DEHNcombo YPV SCI 600: Two-pole combined lightning current and surge arrester for use in photovoltaic power supply systems up to 600 V d.c.
DEHNcombo YPV SCI 1000: Two-pole combined lightning current and surge arrester for use in photovoltaic power supply systems up to 1000 V d.c.
DEHNcombo YPV SCI 1500: Two-pole combined lightning current and surge arrester for use in photovoltaic power supply systems up to 1500 V d.c.
DEHNcombo YPV SCI ... FM: With remote signalling contact for monitoring device (floating changeover contact)

Details

Three-step d.c. switching device (patented SCI principle)
The DEHNcombo YPV SCI ... combined arrester protects equipment in photovoltaic systems against lightning currents.

Thanks to its application-optimised discharge capacity of 6.25 kA (10/350 µs) per pole, DEHNcombo is tailored to meet the requirements of the latest version of the EN 50539-12 standard and Supplement 5 of the German DIN EN 62305-3 standard.
With a short-circuit current rating of 1000 A, DEHNcombo easily meets all requirements placed on surge arresters in small, medium and large photovoltaic systems and can be used without additional backup fuse in all photovoltaic systems up to 1000 A.
Due to its enclosure design which is specifically adapted to the system-specific requirements, even the version for voltages up to 1500 V can be used without taking special precautions (e.g. safety distances). The combined arrester has a width of only four modules, thus allowing space-saving installation.

The patented three-step d.c. switching device (SCI principle) provides an extremely high degree of safety which is required in modern photovoltaic systems. DEHNcombo YPV SCI is available for voltages of 600 V, 1000 V and 1500 V, covering the most common voltage levels of photovoltaic systems.
The fault-resistant Y circuit and the combined disconnection and short-circuiting device further reduce the probability of an arrester failure in case of the operating and fault states which have to be considered in photovoltaic systems. This ensures reliable operation of the PV system at any time.

A low own consumption of the devices is also an important aspect in PV systems. The operating state / fault indication, which needs no power to operate and instantly provides information on the operating state of the arrester, also fulfils this requirement. With its optional floating changeover contact, the remote signal can be used as a break or make contact according to the particular circuit concept.

Models

DEHNcombo YPV SCI ...

DEHNcombo YPV SCI ... FM

DEHNcombo YPV SCI ...

Basic circuit diagram DCB YPV SCI ...Dimension drawing DCB YPV SCI ...

Combined lightning current and surge arrester for use in photovoltaic power supply systems up to 1500 V d.c.


Specifications

Type
Part No.
SPD according to EN 50539-11
Max. PV voltage [DC+ -> DC-] (UCPV)
Max. PV voltage [DC+/DC- -> PE] (UCPV)
Short-circuit current rating (ISCPV)
Nominal discharge current (8/20 µs) (In)
Total discharge current (8/20 µs) [DC+/DC- -> PE] (Itotal)
Total discharge current (10/350 µs) [DC+/DC- -> PE] (Itotal)
Specific energy [DC+/DC- -> PE] (l)
Lightning impulse current (10/350 µs) [DC+ -> PE/DC- -> PE] (Iimp)
Specific energy [DC+ -> PE/DC- -> PE] (W/R)
Voltage protection level [(DC+/DC-) -> PE] (UP)
Voltage protection level [DC+ -> DC-] (UP)
Response time (tA)
Operating temperature range (TU)
Operating state / fault indication
Number of ports
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Place of installation
Degree of protection
Dimensions
Approvals
Extended technical data:
Short-circuit current rating (ISCPV)
Weight
GTIN
PU
Part No.
  • DCB YPV SCI 600
  • 900 060
  • type 1 + type 2
  • ≤ 600 V
  • ≤ 450 V
  • 1000 A
  • 15 kA
  • 30 kA
  • 12.5 kA
  • 39.06 kJ/ohms
  • 6.25 kA
  • 9.76 kJ/ohms
  • 1.75 kV
  • 3 kV
  • 25 ns
  • -40 °C ... +80 °C
  • green / red
  • 1
  • 1,5 mm2 solid / flexible
  • 35 mm2 stranded / 25 mm2 flexible
  • 35 mm DIN rails acc. to EN 60715
  • thermoplastic, red, UL 94 V-0
  • indoor installation
  • IP 20
  • 4 module(s), DIN 43880
  • KEMA, UL
  •  
  •  
  • 374 g
  • 4013364153707
  • 1 pc(s)
  • 900 060
  • Specifications (PDF)
  • More
  • DCB YPV SCI 1000
  • 900 061
  • type 1 + type 2
  • ≤ 1000 V
  • ≤ 725 V
  • 1000 A
  • 15 kA
  • 30 kA
  • 12.5 kA
  • 39.06 kJ/ohms
  • 6.25 kA
  • 9.76 kJ/ohms
  • 2.5 kV
  • 4.75 kV
  • 25 ns
  • -40 °C ... +80 °C
  • green / red
  • 1
  • 1.5 mm2 solid / flexible
  • 35 mm2 stranded / 25 mm2 flexible
  • 35 mm DIN rails acc. to EN 60715
  • thermoplastic, red, UL 94 V-0
  • indoor installation
  • IP 20
  • 4 module(s), DIN 43880
  • KEMA, UL
  • ---------------------------------
  • 2.5 kA
  • 433 g
  • 4013364153721
  • 1 pc(s)
  • 900 061
  • Specifications (PDF)
  • More
  • DCB YPV SCI 1500
  • 900 062
  • type 1 + type 2
  • ≤ 1500 V
  • ≤ 1100 V
  • 1000 A
  • 15 kA
  • 30 kA
  • 12.5 kA
  • 39.06 kJ/ohms
  • 6.25 kA
  • 9.76 kJ/ohms
  • 3.75 kV
  • 7.25 kV
  • 25 ns
  • -40 °C ... +80 °C
  • green / red
  • 1
  • 1.5 mm2 solid / flexible
  • 35 mm2 stranded / 25 mm2 flexible
  • 35 mm DIN rails acc. to EN 60715
  • thermoplastic, red, UL 94 V-0
  • indoor installation
  • IP 20
  • 4 module(s), DIN 43880
  • KEMA
  • ---------------------------------
  • 2.5 kA
  • 524 g
  • 4013364153745
  • 1 pc(s)
  • 900 062
  • Specifications (PDF)
  • More

DEHNcombo YPV SCI ... FM

Basic circuit diagram DCB YPV SCI ... FMDimension drawing DCB YPV SCI ... FM

Combined lightning current and surge arrester for use in photovoltaic power supply systems up to 1500 V d.c.; with floating remote signalling contact.


Specifications

Type
Part No.
SPD according to EN 50539-11
Max. PV voltage [DC+ -> DC-] (UCPV)
Max. PV voltage [DC+/DC- -> PE] (UCPV)
Short-circuit current rating (ISCPV)
Nominal discharge current (8/20 µs) (In)
Total discharge current (8/20 µs) [DC+/DC- -> PE] (Itotal)
Total discharge current (10/350 µs) [DC+/DC- -> PE] (Itotal)
Specific energy [DC+/DC- -> PE] (l)
Lightning impulse current (10/350 µs) [DC+ -> PE/DC- -> PE] (Iimp)
Specific energy [DC+ -> PE/DC- -> PE] (W/R)
Voltage protection level [(DC+/DC-) -> PE] (UP)
Voltage protection level [DC+ -> DC-] (UP)
Response time (tA)
Operating temperature range (TU)
Operating state / fault indication
Number of ports
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Place of installation
Degree of protection
Dimensions
Approvals
Type of remote signalling contact
Switching capacity (a.c.)
Switching capacity (d.c.)
Cross-sectional area for remote signalling terminals
Extended technical data:
Short-circuit current rating (ISCPV)
Weight
GTIN
PU
Part No.
  • DCB YPV SCI 600 FM
  • 900 065
  • type 1 + type 2
  • ≤ 600 V
  • ≤ 450 V
  • 1000 A
  • 15 kA
  • 30 kA
  • 12.5 kA
  • 39.06 kJ/ohms
  • 6.25 kA
  • 9.76 kJ/ohms
  • 1.75 kV
  • 3 kV
  • 25 ns
  • -40 °C ... +80 °C
  • green / red
  • 1
  • 1,5 mm2 solid / flexible
  • 35 mm2 stranded / 25 mm2 flexible
  • 35 mm DIN rails acc. to EN 60715
  • thermoplastic, red, UL 94 V-0
  • indoor installation
  • IP 20
  • 4 module(s), DIN 43880
  • KEMA, UL
  • changeover contact
  • 250 V / 0.5 A
  • 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
  • max. 1.5 mm2 solid / flexible
  •  
  •  
  • 378 g
  • 4013364153714
  • 1 pc(s)
  • 900 065
  • Specifications (PDF)
  • More
  • DCB YPV SCI 1000 FM
  • 900 066
  • type 1 + type 2
  • ≤ 1000 V
  • ≤ 725 V
  • 1000 A
  • 15 kA
  • 30 kA
  • 12.5 kA
  • 39.06 kJ/ohms
  • 6.25 kA
  • 9.76 kJ/ohms
  • 2.5 kV
  • 4.75 kV
  • 25 ns
  • -40 °C ... +80 °C
  • green / red
  • 1
  • 1,5 mm2 solid / flexible
  • 35 mm2 stranded / 25 mm2 flexible
  • 35 mm DIN rails acc. to EN 60715
  • thermoplastic, red, UL 94 V-0
  • indoor installation
  • IP 20
  • 4 module(s), DIN 43880
  • KEMA, UL
  • changeover contact
  • 250 V / 0.5 A
  • 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
  • max. 1.5 mm2 solid / flexible
  • ---------------------------------
  • 2.5 kA
  • 437 g
  • 4013364153738
  • 1 pc(s)
  • 900 066
  • Specifications (PDF)
  • More
  • DCB YPV SCI 1500 FM
  • 900 067
  • type 1 + type 2
  • ≤ 1500 V
  • ≤ 1100 V
  • 1000 A
  • 15 kA
  • 30 kA
  • 12.5 kA
  • 39.06 kJ/ohms
  • 6.25 kA
  • 9.76 kJ/ohms
  • 3.75 kV
  • 7.25 kV
  • 25 ns
  • -40 °C ... +80 °C
  • green / red
  • 1
  • 1.5 mm2 solid / flexible
  • 35 mm2 stranded / 25 mm2 flexible
  • 35 mm DIN rails acc. to EN 60715
  • thermoplastic, red, UL 94 V-0
  • indoor installation
  • IP 20
  • 4 module(s), DIN 43880
  • KEMA
  • changeover contact
  • 250 V / 0.5 A
  • 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
  • max. 1.5 mm2 solid / flexible
  • ---------------------------------
  • 2.5 kA
  • 530 g
  • 4013364153752
  • 1 pc(s)
  • 900 067
  • Specifications (PDF)
  • More